Proline t-mass 65 MODBUS RS485
SENSOR DATA
Hauser
49
INTERNAL DIAMETER
Prerequisite
This function is
only
available for insertion sensors (t-mass 65I).
This function is
only
available if CIRCULAR is selected in the function PIPE
47) and OTHER was selected in the function PIPE STANDARD
47).
Description
Use this function to view the internal diameter of a circular pipe.
The unit is taken from the function UNIT LENGTH (
10).
Display
5-digit floating-point number
60 to 99999 (mm) or 2.362 to 3937 (inch) (country dependent
55)
MODBUS register:
Data type:
Access:
9604
Float
read
INTERNAL HEIGHT
Prerequisite
This function is
only
available for insertion sensors (t-mass 65I).
This function is
only
available if RETANGLUAR was selected in the function
47).
Description
Use this function to enter the internal height of a rectangular duct.
The unit is taken from the function UNIT LENGTH (
10).
User input
5-digit floating-point number
45 to 99999 (mm) or 1.771 to 3937 (inch) (country dependent
55)
Factory setting
150.0 (mm) or 6.0 (inch) (country dependent
55)
MODBUS register:
Data type:
Access:
9606
Float
read/write
INTERNAL WIDTH
Prerequisite
This function is
only
available for insertion sensors (t-mass 65I).
This function is
only
available if RECTANGULAR was selected in the PIPE
TYPE function (
47).
Description
Use this function to enter the internal width of a rectangular duct.
The unit is taken from the function UNIT LENGTH (
10).
User input
5-digit floating-point number
45 to 99999 (mm) or 1.771 to 3937 (inch) (country dependent
55)
Factory setting
150.0 (mm) or 6.0 (inch) (country dependent
55)
MODBUS register:
Data type:
Access:
9608
Float
read/write
MOUNTING
Prerequisite
This function is
only
available for insertion sensors (t-mass 65I).
This function is
only
available if RECTANGULAR is selected in the function
47).
Description
Use this function to select the installation direction of the insertion sensor in the
rectangular duct.
– If the VERTICAL option is selected, the value from the function
49) is used to calculate the insertion depth
– If the HORIZONTAL option is selected, the value from the function
49) is used to calculate the insertion depth
Options
0 = HORIZONTAL
1 = VERTICAL
Factory setting
VERTICAL
MODBUS register:
Data type:
Access:
9628
Integer
read/write
Function description, SENSOR DATA group