Proline t-mass 65 MODBUS RS485
SUPERVISION
Hauser
51
17
SUPERVISION
Function description, SUPERVISION group
ACTUAL SYSTEM CONDITION
Description
The current system status appears on the display.
Display
SYSTEM OK or
The fault/notice message with the highest priority.
MODBUS error codes: Operating Instructions BA00115D/06
MODBUS register:
Data type:
MODBUS register:
Data type:
Access:
6859
Integer
read
6821
String (16)
PREVIOUS SYSTEM
CONDITION
Description
The last 16 fault and notice messages appear on the display.
MODBUS error codes: Operating Instructions BA00115D/06
MODBUS register:
Data type:
MODBUS register:
Data type:
Access:
6830
String (16)
6860…6875
Integer
read
ALARM DELAY
Description
Use this function to enter a time delay for which the criteria for an error
always has to be satisfied before a fault or notice message is generated.
Depending on the setting and the type of error, this suppression acts on the
display and MODBUS Communication.
!
Note!
If this function is activated fault and notice messages are delayed by the time
corresponding to the setting before being forwarded to the MODBUS
communication. Therefore, check in advance whether a delay of this nature
could affect the safety requirements of the process. If fault and notice messages
are not be suppressed, than a value of 0 seconds must be entered here.
User input
0 to 100 s (in steps of one second)
Factory setting
0 s
MODBUS register:
Data type:
Access:
6808
Float
read/write
SYSTEM RESET
Description
Use this function to restart (reset) the measuring device.
Options
0 = NO
The device is not restarted.
1 = RESTART SYSTEM
Restart without disconnecting main power. In doing so, all the data (functions)
are accepted unchanged.
Factory setting
NO
MODBUS register:
Data type:
Access:
6817
Integer
read/write
OPERATION HOURS
Description
The hours of operation of the device appear on the display.
Display
Depends on the number of hours of operation elapsed:
Hours of operation < 10 hours
display format = 0:00:00 (hr:min:sec)
Hours of operation 10 to 10 000 hours
display format = 0000:00 (hr:min)
Hours of operation >10 000 hours
display format = 000000 (hr)
MODBUS register:
Data type:
Access:
6810
Float
read
HOURS SINCE RESET
Description
The hours of operation since the last reset of the device appear on the display.
Display
Depends on the number of hours of operation elapsed:
Hours of operation < 10 hours
display format = 0:00:00 (hr:min:sec)
Hours of operation 10 to 10 000 hours
display format = 0000:00 (hr:min)
Hours of operation >10 000 hours
display format = 000000 (hr)
MODBUS register:
Data type:
Access:
6878
Float
read