SENSOR DATA
Hauser
47
16
SENSOR DATA
Function description, SENSOR DATA group
This group of functions contains the essential data relating to the sensor geometry and calibration.
Flange version (t-mass 65F): The sensor data cannot be changed and is read only.
Insertion version (t-mass 65I): The sensor data can be changed to suit the application pipe.
The pipe or duct dimensions are essential for calculating the correct insertion depth.
All the sensor's parameter settings are saved on the HistoROM/S-DAT memory chip.
!
Note!
See the flowchart of the QUICK SETUP SENSOR
11.
PIPE TYPE
Prerequisite
This function is
only
available for insertion sensors (t-mass 65I).
Description
Use this function to select the type of pipe.
Options
0 = CIRCULAR
1 = RECTANGULAR
Factory setting
CIRCULAR
MODBUS register:
Data type:
Access:
9603
Integer
read/write
PIPE STANDARD
Prerequisite
This function is
only
available for insertion sensors (t-mass 65I).
This function is
not
available if RECTANGULAR is selected in the PIPE TYPE
function (
47).
Description
Use this function to select a pipe standard.
If the option OTHERS is selected here, then values need to be entered in the
functions OUTER DIAMETER and WALL THICKNESS.
Options
ANSI B3610
0 = SCHEDULE 10
1 = SCHEDULE 20
2 = SCHEDULE 30
3 = SCHEDULE 40
4 = SCHEDULE 60
5 = SCHEDULE 80
ANSI B3619
6 = SCHEDULE 10
7 = SCHEDULE 40
8 = SCHEDULE 80
DIN
9 = PN6
10 = PN10
11 = PN16
12 = PN25
13 = PN40
14 = OTHERS
Factory setting
PN10 or B36.10 SCHEDULE 10 (country dependent
MODBUS register:
Data type:
Access:
9631
Integer
read/write