Function description, GAS group
SELECT GROUP
Description
Use this function to:
• select a gas group for editing
• set the active gas group manually
Setting the active gas group:
• On completion of programming all the necessary functions in the gas group,
select YES in the SAVE CHANGES function
43, or
• If the gas group is already programmed as required, simply select the required
gas group and then exit using the ESC keys (
X
).
Options
0 = GAS GROUP 1
1 = GAS GROUP 2
Factory setting
GAS GROUP 1
MODBUS Register
Datentyp:
Zugriff
9798
Integer
read/write
NUMBER OF GASES
Description
Use this function to enter the number of gases that are used in the gas group.
User input
1 to 8
Factory setting
1
MODBUS register:
Data type:
Access:
9717
Float
read/write
GAS TYPE 1
Description
Use this function to select gas type 1.
Options
0 = AIR
1 = AMMONIA
2 = ARGON
3 = BUTANE
4 = CARBON DIOXIDE
5 = CARBON MONOXIDE
6 = CHLORINE
7 = ETHANE
8 = ETHYLENE
9 = HELIUM 4
10 = HYDROGEN NORMAL
11 = HYDROGEN CHLORIDE
12 = HYDROGEN SULFIDE
13 = KRYPTON
14 = METHANE
15 = NEON
16 = NITROGEN
17 = OXYGEN
18 = PROPANE
20 = XENON
22 = NOT USED
23 = SPECIAL GAS
Factory setting
AIR
MODBUS register:
Data type:
Access:
9719
Integer
read/write
MOLE % GAS 1
Prerequisite
This function is
not
available if the setting in NUMBER OF GASES (
40)
is 1. (The factory setting 100% is automatically used)
Description
Use this function to enter the Mole % of the gas selected in GAS TYPE 1.
User input
000.00 % to 100.00 %
Factory setting
100.00 %
MODBUS register:
Data type:
Access:
9720
Float
read/write