Fieldgate FXA42
Operation
Hauser
51
Unit
Description
In
Min
MinEn
Max
MaxEn
Sig Limit
A0034298-EN
This unit can be used to limit the value of the input port
In
. If
In
is less than
Min
and the minimum
limit is activated by the Boolean input port
MinEn
, the output is set to
Min
. If
In
is greater than
Max
and the maximum limit is activated by the Boolean input port
MaxEn
, the output is set to
Max
.
Max
In
Out
Min
A0034329
The limitation is performed in the largest numeric data type of all the output ports that are
connected to the input ports
In
,
Min
and
Max
of the unit. These input ports and the output port
adopt this data type.
In
TUp
TDown
Force
Sig Smooth
A0034299-EN
This unit is used to smooth a signal. If the value of the input port
In
changes, the value of the output
port will be approximated to this new value using an exponential function.
The value of the input port
TUp
(32-bit unsigned integer) refers to the time (in ms) that is needed to
reach the new value if the old value is less than the new value.
The value of the input port
TDown
(32-bit unsigned integer) refers to the time (in ms) that is needed
to reach the new value if the old value is greater than the new value.
100 %
100 %
In
In
Out
50 %
50 %
0 %
0 %
(-t)
(-t)
0t
0t
IPO Cycle = t
IPO Cycle = t
TUp = 5t
TDown = 5t
t
t
2t
2t
3t
3t
4t
4t
5t
5t
Out
A0034330
If the Boolean input port
Force
is set, the value of the input port
In
is copied immediately to the output
port.
The smoothing is performed in the numeric data type of the output port that is connected to the input
port
In
of the unit. The input port
In
and the output port adopt this data type.
In
GradUp
GradDown
Force
En
Sig Track
A0034305
This unit is used to limit the gradient of a signal. If the value of the input port
In
changes, the value of
the output port follows this new value using a linear function.
The value of the input port
GradUp
defines the maximum slope of this linear function per second if the
new value is greater than the old value. The value of the input port
GradDown
defines the maximum
slope of this linear function per second if the new value is less than the old value. Both gradients must
be positive numbers.
200
200
In
In
Out
150
150
100
100
0s
0s
GradUp = 30
GradDown = 40
1s
1s
2s
2s
3s
3s
4s
4s
5s
5s
Out
A0034331
If the Boolean input port
Force
is set, the value of the input port
In
is copied immediately to the output
port.
The Boolean input port
En
can be used to enable the unit. If the value is
0
, the output port is always
0
.
The tracking is performed in the largest numeric data type of all the output ports that are connected
to the input ports
In
,
GradUp
or
GradDown
. These input ports and the output port adopt this data type.