Operation
Fieldgate FXA42
48
Hauser
Unit
Description
SetOn
SetOff
Act
En
On/Off Ctrl
A0034234-EN
This unit represents an on/off controller.
The input ports
SetOn
,
SetOff
and
Act
adopt the largest numeric data type of all the output ports that
are connected to one of these input ports.
The unit switches its Boolean output port on or off if the value of the input port
Act
exceeds or drops
below the values of the input ports
SetOn
and
SetOff
respectively. The Boolean input port
En
can be
used to enable the unit. If the value is
0
, the output port is always
0
.
If
SetOn
=
SetOff
, the unit behaves as illustrated in the diagram below. The output port is switched on
when
Act
>
SetOn
. The output port is switched off when
Act
≤
SetOff
.
SetOn = SetOff
SetOn/SetOff
Act
1
0
A0034326
If
SetOn
>
SetOff
, the unit behaves as illustrated in the diagram below. The output port is switched on
when
Act
≥
SetOn
(broken blue line). The output port is switched off when
Act
≤
SetOff
(solid blue
line).
SetOn > SetOff
SetOff
SetOn
Act
1
0
A0034601
If
SetOn
<
SetOff
, the unit behaves as illustrated in the diagram below. The output port is switched on
when
Act
≤
SetOn
(solid blue line). The output port is switched off when
Act
≤
SetOff
(broken blue
line).
SetOn < SetOff
Act
1
0
SetOn
SetOff
A0034602
Running
Connected
Start
Stop
OpenVPN
A0034235
This unit can be used to control the OpenVPN client.
The client is started when the Boolean input port
Start
switches from
0
to
1
. The client is stopped
when the Boolean input port
Stop
switches from
0
to
1
.
The Boolean output port
Running
indicates whether the client is running. The Boolean output port
Connected
indicates whether the client is connected to a server.
Or
A0034237-EN
This unit performs a binary OR. The operation is performed in the largest integer data type of all the
output ports that are connected to the input ports of the unit. All the ports of the unit adopt this data
type. Input ports connected to floating point or string output ports are treated as if they were
connected to a 32-bit signed integer output port.
Examples:
•
0
and
0
⇒
0
•
0
and
1
⇒
1
•
1
and
1
⇒
1
•
3 (0011
2
)
and
8 (1000
2
)
⇒
11 (1011
2
)