This unit represents a timer on-delay.
The timer is started when the Boolean input port
IN
switches to
1
. The output port
ET
(elapsed time,
32-bit unsigned integer) indicates how much time, in milliseconds, has elapsed since the timer was
started. When the value of the output port
ET
reaches the value of the input port
PT
(preset time, 32-
bit unsigned integer) the timer is stopped and the Boolean output port
Q
is reset. The output port
Q
is
reset when the input port
IN
switches to
0
.
IN
ET
Q
← →
PT
A0034333
Note that if the value of the input port
Int
is less than the cycle time or not divisible by the cycle time,
the value is rounded up internally to the nearest multiple of the cycle time.
IN
PT
TP
Q
ET
A0034311
This unit represents a timer pulse.
When the Boolean input port
IN
switches to
1
, the Boolean output port
Q
is set to
1
and the timer is
started. The output port
ET
(elapsed time, 32-bit unsigned integer) indicates how much time, in
milliseconds, has elapsed since the timer was started. When the value of the output port
ET
reaches
the value of the input port
PT
(preset time, 32-bit unsigned integer) the timer is stopped and the
output port
Q
is reset to
0
.
IN
ET
Q
← →
PT
← →
PT
A0034334
Note that if the value of the input port
Int
is less than the cycle time or not divisible by the cycle time,
the value is rounded up internally to the nearest multiple of the cycle time.
Trigger
A0034312
This unit represents a trigger. It sets its Boolean output port to
1
for an IPO cycle if it detects a rising
edge on one of its Boolean inputs.
Negate the input port to detect a falling edge.
To detect a rising or a falling edge, connect the same input signal to two of the trigger's input ports
and negate one of them.