Operation
Fieldgate FXA42
90
Hauser
System clock updated from RTC
The system clock has just been updated with the time from the real-time clock.
Could not get exclusive access to clock(s).
The system time manager could not get exclusive access to the system clock and (if
available) the real-time clock. Thus the system clock could not be set or the real-time clock
could not be read.
Daylight saving time rules will be used up within the next two years.
The firmware of the device includes daylight saving time rules for a limited time period.
New rules will be added with new firmware versions. This message indicates that the rules
will be used up within the next 2 years. Run a firmware update to get new rules.
SNTP client error: <message>
The SNTP client has returned the error message shown.
RTC not available
The device should feature a real-time clock, but it cannot be accessed.
Could not write to RTC: <message>
Failed to set the real-time clock. The message also shows an error message returned by the
real-time clock driver.
Could not read from RTC: <message>
The real-time clock could not be read. The message also shows an error message returned
by the real-time clock driver.
Could not read daylight saving time file.
The daylight saving time file for this time zone is missing or corrupted.
No daylight saving time rule found for the current time.
No daylight saving time rule could be found for the current time. This means that either
the daylight saving time rules are outdated or that the device's time is set incorrectly.
DNS error (<error code>) for server <server name/IP>
The SNTP client could not determine the IP address of the server with the name indicated.
The message also shows the error code returned by the TCP/IP stack.
Could not open socket for server <server name/IP>
The SNTP client could not open a UDP socket in order to contact the time server with the
name or IP address indicated.
Could not send to server <server name/IP>
The SNTP client could not send a request to the time server with the name or IP address
indicated.
Failed to receive reply from server <server name/IP>
The SNTP client could not receive a reply from the time server with the name or IP address
indicated.
Unexpected packet format from server <server name/IP>
The SNTP client received an invalid reply from the time server with the name or IP address
indicated.
Timestamps not plausible from server <server name/IP>
The SNTP client received a reply with implausible timestamps from the time server with
the name or IP address indicated.
Содержание Fieldgate FXA42
Страница 118: ...www addresses endress com 71483585 71483585 ...