Technical data
Fieldgate FXA42
112
Hauser
A
B
C
D
X1 = 11 21 31 41 4 x GND
X3 = 13 23 33 43 4 x 4 to 20 mA analog input
Maximum input voltage: 35 V
Maximum input current: 22 mA
Internal resistance: 250 Ω (suitable for
HART communication)
X4 = 14 24 34 44 4 x auxiliary voltage output for
transmitter loop power supply
Output voltage: 28 V
DC
(no-load)
26 V
DC
@ 3 mA
20 V
DC
@ 30 mA
Output current: max. 160 mA
4 to 20 mA analog input (4-wire)
X1 X2 X3 X4
4W:
A0031283
A
B
C
D
41
42
43
44
31
32
33
34
21
22
23
24
11
12
13
14
A0031499
Terminal block
Function
Properties
A
B
C
D
X1 = 11 21 31 41 4 x GND
X3 = 13 23 33 43 4 x 4 to 20 mA analog input
Maximum input voltage: 35 V
Maximum input current: 22 mA
Internal resistance: 250 Ω (suitable for
HART communication)
13.1.6 Digital input
Digital input (2-wire) with auxiliary voltage output
X1 X2 X3 X4
2W:
A0031284
A
B
C
D
41
42
43
44
31
32
33
34
21
22
23
24
11
12
13
14
A0031499
Terminal block
Function
Properties
A
B
C
D