Pin
Signal
P2.1
Channel 1, (+) 4 (0)–20 mA
P2.2
Channel 1, GND
P2.3
Channel 2, (+) 4 (0)–20 mA
P2.4
Channel 2, GND
P2.5
Channel 3, (+) 4 (0)–20 mA
P2.6
Channel 3, GND
P2.7
Channel 4, (+) 4 (0)–20 mA
P2.8
Channel 4, GND
P2.9
Channel 5, (+) 4 (0)–20 mA
P2.10
Channel 5, GND
P2.11
not used
P2.12
not used
P3.1
not used
P3.2
not used
P3.3
Output 1 (Failure), NC
P3.4
Output 1 (Failure), NO
P3.5
Output 1 (Failure), COM
P3.6
Output 2 (Maintenance Request), NC
P3.7
Output 2 (Maintenance Request), NO
P3.8
Output 2 (Maintenance Request), COM
P3.9
Output 3 (Out of Spec), NC
P3.10
Output 3 (Out of Spec), NO
P3.11
Output 3 (Out of Spec), COM
P3.12
Output 4 (Function check), NC
P4.1
Output 4 (Function check), NO
P4.2
Output 4 (Function check), COM
P4.3
not used
P4.4
P4.5
P4.6
P4.7
P4.8
P4.9
P4.10
P4.11
P4.12
Relay Outputs
**)
Analog Outputs
Serial Interface
*)
4.6.1 Installation - X-STREAM XEGK, X-STREAM XEGP
Fig. 4-9:
Configuration of XSTA
Terminal Adapter
To connect any serial interface, the adapter is
equipped with a flat flexible cable ending in a
9-pin submin-D plug, which should be plugged
onto the unit’s X2 connector.
1 Connector for plug X1 (on reverse side)
2 Connection for flat cable to plug X2 (cable not illustrated)
3 Screw-type terminals
Note!
Consider the installation notes in
section
The XSTA adapter can optionally be used (not
XEGK) to connect signal cables to screw-
type terminals instead of submin-D plugs and
sockets: it is plugged onto the X1 Submin-D
connector on the unit.
1
2
3
Assignment of serial interface terminals
*)
See table below
**)
Configuration of relay output termi
-
nals as per standard factory setting
(NAMUR status signals)
Recommended
wire gauge:
0.14…1.5 mm
2
(AWG 26…AWG 16)
end sleeves not re-
quired
Skinning length: 5 mm (0.2")
Thread:
M2
Min. tightening
torque:
0.25 Nm
(2.21 in.lb)
Terminal
MOD 485/
2 wire
MOD 485/
4 wire
RS 232
P4.4
SER1
Common Common Common
P4.5
SER2
not used
not used
RXD
P4.6
SER3
not used
not used
TXD
P4.7
SER4
not used
RXD1(+)
not used
P4.8
SER5
D1(+)
TXD1(+)
Common
P4.9
SER6
not used
not used
not used
P4.10
7
not used
not used
not used
P4.11
8
not used
RXD0(-)
not used
P4.12
9
D0(-)
TXD0(-)
not used
Содержание Rosemount X-Stream Series
Страница 370: ...Emerson Process Management GmbH Co OHG 7 82 X STREAM XE Instruction Manual HASXEE IM HS 10 2012 ...
Страница 414: ...Emerson Process Management GmbH Co OHG 8 44 X STREAM XE Instruction Manual HASXEE IM HS 10 2012 ...
Страница 486: ...Emerson Process Management GmbH Co OHG A 4 X STREAM XE Instruction Manual HASXEE IM HS 10 2012 A 1 Modbus Specification ...
Страница 488: ...Emerson Process Management GmbH Co OHG A 6 X STREAM XE Instruction Manual HASXEE IM HS 10 2012 A 1 Modbus Specification ...
Страница 490: ...Emerson Process Management GmbH Co OHG A 8 X STREAM XE Instruction Manual HASXEE IM HS 10 2012 A 1 Modbus Specification ...
Страница 526: ...Emerson Process Management GmbH Co OHG A 44 X STREAM XE Instruction Manual HASXEE IM HS 10 2012 ...
Страница 535: ......