Procedure
1.
Make a service port connection from ProLink III to your transmitter.
2.
Choose Device Tools > Configuration > Weights & Measuresand set Regulatory
Agency to the apropriate regulatory agency for your application.
Option
Description
NTEP
Regulatory agency for the U.S.A. and Canada
OIML
Regulatory agency for all other world areas
3.
Choose Device Tools > Configuration > Totalizer Control Methods and set totalizer
control methods as desired.
Parameter
Option
Reset Totalizers from Display
•
Enabled: You can reset totalizers from the display,
whether or not the transmitter is secured.
•
Disabled: You can reset totalizers from the display only
when the transmitter is unsecured.
Reset Totalizers via Remote
Communications
•
Enabled: You can reset totalizers using digital communi-
cations, whether or not the transmitter is secured.
•
Disabled: You can reset totalizers using digital communi-
cations only when the transmitter is unsecured.
Digital communications
refers to any method that uses Modbus or HART
communications to interact with the transmitter. This includes ProLink III, the
Field Communicator, and any host.
4.
If required for your installation, configure your transmitters for two frequency
outputs and set them to operate in Quadrature mode.
a. Choose Device Tools > Configuration > I/O > Channels.
b. For Channel B, set Channel Typeto
Frequency Output
and click Apply.
c. For Channel C, set Channel Typeto
Frequency Output
and click Apply.
d. Choose Device Tools > Configuration > I/O > Outputs > Frequency Output Mode
and select
Quadrature
.
5.
If required for your installation, choose Device Tools > Configuration > Transmitter
Display > Display Security, then enable and configure a password for the alarm
menu.
Security for the alarm menu is required under German law for PTB-type approval for
gas applications.
6.
If required for your installation, choose Device Tools > Device Information, then read
and record the firmware checksum values for the transmitter and the core
processor.
Set up the Weights & Measures application
Configuration and Use Manual
119
Содержание Micro Motion 2500
Страница 8: ...Contents vi Micro Motion Model 2500 Transmitters with Configurable Input Outputs ...
Страница 10: ...Getting started 2 Micro Motion Model 2500 Transmitters with Configurable Input Outputs ...
Страница 18: ...Quick start 10 Micro Motion Model 2500 Transmitters with Configurable Input Outputs ...
Страница 20: ...Configuration and commissioning 12 Micro Motion Model 2500 Transmitters with Configurable Input Outputs ...
Страница 124: ...Complete the configuration 116 Micro Motion Model 2500 Transmitters with Configurable Input Outputs ...
Страница 130: ...Set up the Weights Measures application 122 Micro Motion Model 2500 Transmitters with Configurable Input Outputs ...
Страница 132: ...Operations maintenance and troubleshooting 124 Micro Motion Model 2500 Transmitters with Configurable Input Outputs ...
Страница 140: ...Transmitter operation 132 Micro Motion Model 2500 Transmitters with Configurable Input Outputs ...
Страница 216: ...Using ProLink III with the transmitter 208 Micro Motion Model 2500 Transmitters with Configurable Input Outputs ...
Страница 226: ...Default values and ranges 218 Micro Motion Model 2500 Transmitters with Configurable Input Outputs ...
Страница 237: ...NE 53 history Configuration and Use Manual 229 ...