4.5.4
Configure Density Cutoff
Density Cutoff specifies the lowest density value that will be reported as measured. All
density values below this cutoff will be reported as 0.
Procedure
Set Density Cutoff to the value you want to use.
For most applications, the default setting (0.2 g/cm
³
) is sufficient. The range is 0.0 g/cm
³
to 0.5 g/cm
³
.
Effect of Density Cutoff on volume measurement
Density Cutoff affects liquid volume measurement. If the density value goes below Density
Cutoff, the volume flow rate is reported as 0. Density Cutoff does not affect gas standard
volume measurement. Gas standard volume values are always calculated from the value
configured for Standard Gas Density or polled value if configured for polled base density.
4.6
Configure temperature measurement
The temperature measurement parameters control how temperature data from the
sensor is reported.
4.6.1
Configure Temperature Measurement Unit
ProLink III
Device Tools > Configuration > Process Measurement > Temperature
Field Communicator Configure > Manual Setup > Measurements > Temperature > Temperature Unit
Overview
Temperature Measurement Unit specifies the unit that will be used for temperature
measurement.
Procedure
Set Temperature Measurement Unit to the option you want to use.
The default setting is
Degrees Celsius
.
Options for Temperature Measurement Unit
The transmitter provides a standard set of units for Temperature Measurement Unit.
Different communications tools may use different labels for the units.
Configure process measurement
42
Micro Motion Model 2500 Transmitters with Configurable Input/Outputs
Содержание Micro Motion 2500
Страница 8: ...Contents vi Micro Motion Model 2500 Transmitters with Configurable Input Outputs ...
Страница 10: ...Getting started 2 Micro Motion Model 2500 Transmitters with Configurable Input Outputs ...
Страница 18: ...Quick start 10 Micro Motion Model 2500 Transmitters with Configurable Input Outputs ...
Страница 20: ...Configuration and commissioning 12 Micro Motion Model 2500 Transmitters with Configurable Input Outputs ...
Страница 124: ...Complete the configuration 116 Micro Motion Model 2500 Transmitters with Configurable Input Outputs ...
Страница 130: ...Set up the Weights Measures application 122 Micro Motion Model 2500 Transmitters with Configurable Input Outputs ...
Страница 132: ...Operations maintenance and troubleshooting 124 Micro Motion Model 2500 Transmitters with Configurable Input Outputs ...
Страница 140: ...Transmitter operation 132 Micro Motion Model 2500 Transmitters with Configurable Input Outputs ...
Страница 216: ...Using ProLink III with the transmitter 208 Micro Motion Model 2500 Transmitters with Configurable Input Outputs ...
Страница 226: ...Default values and ranges 218 Micro Motion Model 2500 Transmitters with Configurable Input Outputs ...
Страница 237: ...NE 53 history Configuration and Use Manual 229 ...