The default setting is
None
.
Restrictions
•
If mA Output Fault Action or Frequency Output Fault Action is set to
None
, Digital
Communications Fault Action should also be set to
None
. If you do not, the output will not report
actual process data, and this may result in measurement errors or unintended consequences for
your process.
•
If you set Digital Communications Fault Action to
NAN
, you cannot set mA Output Fault Action or
Frequency Output Fault Action to
None
. If you try to do this, the transmitter will not accept the
configuration.
Options for Digital Communications Fault Action
Label
Description
ProLink III
Field Communicator
Upscale
Upscale
•
Process variable values indicate that the val-
ue is greater than the upper sensor limit.
•
Totalizers stop incrementing.
Downscale
Downscale
•
Process variable values indicate that the val-
ue is lower than the lower sensor limit.
•
Totalizers stop incrementing.
Zero
IntZero-All 0
•
Flow rate variables go to the value that rep-
resents a flow rate of 0 (zero).
•
Density is reported as
0
.
•
Temperature is reported as
0 °C
, or the
equivalent if other units are used (e.g.,
32 °F
.
•
Drive gain is reported as measured.
•
Totalizers stop incrementing.
Not a Number
Not-a-Number
•
Process variables are reported as
IEEE
NAN
.
•
Drive gain is reported as measured.
•
Modbus scaled integers are reported as
Max
Int
.
•
Totalizers stop incrementing.
Flow to Zero
IntZero-Flow 0
•
Flow rates are reported as
0
.
•
Other process variables are reported as
measured.
•
Totalizers stop incrementing.
None
None
(default)
•
All process variables are reported as meas-
ured.
•
Totalizers increment if they are running.
Integrate the meter with the control system
Configuration and Use Manual
111
Содержание Micro Motion 2500
Страница 8: ...Contents vi Micro Motion Model 2500 Transmitters with Configurable Input Outputs ...
Страница 10: ...Getting started 2 Micro Motion Model 2500 Transmitters with Configurable Input Outputs ...
Страница 18: ...Quick start 10 Micro Motion Model 2500 Transmitters with Configurable Input Outputs ...
Страница 20: ...Configuration and commissioning 12 Micro Motion Model 2500 Transmitters with Configurable Input Outputs ...
Страница 124: ...Complete the configuration 116 Micro Motion Model 2500 Transmitters with Configurable Input Outputs ...
Страница 130: ...Set up the Weights Measures application 122 Micro Motion Model 2500 Transmitters with Configurable Input Outputs ...
Страница 132: ...Operations maintenance and troubleshooting 124 Micro Motion Model 2500 Transmitters with Configurable Input Outputs ...
Страница 140: ...Transmitter operation 132 Micro Motion Model 2500 Transmitters with Configurable Input Outputs ...
Страница 216: ...Using ProLink III with the transmitter 208 Micro Motion Model 2500 Transmitters with Configurable Input Outputs ...
Страница 226: ...Default values and ranges 218 Micro Motion Model 2500 Transmitters with Configurable Input Outputs ...
Страница 237: ...NE 53 history Configuration and Use Manual 229 ...