Floor-stand Dimensions—Units with EC Fans
41
Liebert
®
CW
™
System Design Manual
Figure 4-18 Floor-stand and floor-planning dimensions, downflow, CW051 and CW060 with EC fans
NOTE:
1. This floor stand should be used when EC fans are intended to be lowered under
a raised floor. The standard Liebert CW floor stand can be used if the fans are to
remain in their original raised position.
2. All paneled sides of unit overhang floorstand 1” (25mm).
3. The floor stand used with EC units is not symmetrical and its orientation to the
Liebert CW is critical for lowering the EC fans. Unless the floor stand is installed in
the correct position, the blowers will not lower into the floor stand.
4. Jack and jack support are shipped loose and are intended to be placed into position
under each fan and utilized to lower or raise that fan as needed.
5. Does not apply to 24 " high floorstand.
*Leveling feet are provided with 1-1/2” (38mm) adjustment from nominal height “A”.
See note 4
1"
25mm
15 3/4"
400mm
3/4"
19mm
31 9/16"
801mm
CENTER FEET
3/4"
19mm
70 9/16"
1792mm
CENTER FEET
3/4"
20mm
72"
1829mm
7/8"
23mm
3"
76mm
73 9/16"
1868mm
A*
33"
838mm
19 1/4"
489mm
Piping access area
5
DPN003211
Rev. 1
Height, in. (mm)
A*
24 (610)
30 (762)
36 (914)
42 (1067)
48 (1219)
Содержание CW089
Страница 2: ......
Страница 8: ...Liebert CW System Design Manual vi ...
Страница 10: ...Liebert CW System Design Manual vi Page intentionally left blank ...
Страница 18: ...Nomenclature and Components Liebert CW System Design Manual 8 Page intentionally left blank ...
Страница 62: ...Dimensions Liebert CW System Design Manual 52 Page intentionally left blank ...
Страница 76: ...Piping Liebert CW System Design Manual 66 Page intentionally left blank ...
Страница 90: ...Electrical Field Connections Liebert CW System Design Manual 80 Page intentionally left blank ...
Страница 114: ...Optional Liebert Air Economizer for Liebert CW Liebert CW System Design Manual 104 Page intentionally left blank ...