Optional Configuration for Liebert CW Seismic Application
Liebert
®
CW
™
System Design Manual
94
Figure A-10 Seismic piping considerations
Anchor piping
to unit
Prefabricated seismic
compensation piping
Unit
FLOOR MOUNT
Secure pipes to floorstand
Prefabricated seismic
compensation piping
Unit
Anchor Piping
FLOORSTAND MOUNT
Seismic compensation device
Upflow with floorstand: anchor to floorstand
Upflow rigid mount: anchor to unit
Downflow: anchor to floorstand
Anchor to
foundation
To unit
FLEXIBLE LOOP EXAMPLE
Flexible Loops:
All units, either rigidly mounted or mounted on vibration isolators, shall be attached to the piping system using flexible loops designed for seismic
movement. Flexible loops shall be capable of movement in the ±X, ±Y, and ±Z planes and must completely isolate the equipment from the piping.
The loops shall be suitable for an operating pressure and temperature of the system, refer to Liebert installation instructions. This includes 1/4"
copper humidifier supply, condensate drainage, and chilled water supply and return. Follow manufacturer’s installation instructions for proper
seismic application of flexible loops.
DPN003209
Pg. 9 Rev. 2
Содержание CW089
Страница 2: ......
Страница 8: ...Liebert CW System Design Manual vi ...
Страница 10: ...Liebert CW System Design Manual vi Page intentionally left blank ...
Страница 18: ...Nomenclature and Components Liebert CW System Design Manual 8 Page intentionally left blank ...
Страница 62: ...Dimensions Liebert CW System Design Manual 52 Page intentionally left blank ...
Страница 76: ...Piping Liebert CW System Design Manual 66 Page intentionally left blank ...
Страница 90: ...Electrical Field Connections Liebert CW System Design Manual 80 Page intentionally left blank ...
Страница 114: ...Optional Liebert Air Economizer for Liebert CW Liebert CW System Design Manual 104 Page intentionally left blank ...