Cabinet and Floor-planning Dimensions—Downflow Models with EC Fans
31
Liebert
®
CW
™
System Design Manual
Figure 4-8 Cabinet and floor-planning dimensions, downflow,
CW300, CW400 with EC fans and filter plenums
(2) Cabinets
Filter Plenum
(shipped separately)
Shaded area indicates the minimum required area below
the unit to be unobstructed for the skirted floorstand
and fan service clearance.
Filters are removed by removing
front panel of the plenum.
Striated area indicates the recommended
minimum clearance to be provided for
component access.
1"
25mm
45"
1143mm
92"
2337mm
1"
25mm
91"
2311mm
120"
3048mm
122"
3099mm
1 1/2"
38mm
76"
1930mm
94"
2388mm
18"
457mm
5/16"
8mm
Bezel
87"
2210mm
Opening
118"
2997mm
Opening
48"
1219mm
36"
914mm
24"
610mm
1 3/4"
44mm
Handle
Notes:
1. Plenums shipped separately.
2. Reference DPN001693 for the electrical
and plumbing requirements.
DPN003218
Rev. 1
Содержание CW089
Страница 2: ......
Страница 8: ...Liebert CW System Design Manual vi ...
Страница 10: ...Liebert CW System Design Manual vi Page intentionally left blank ...
Страница 18: ...Nomenclature and Components Liebert CW System Design Manual 8 Page intentionally left blank ...
Страница 62: ...Dimensions Liebert CW System Design Manual 52 Page intentionally left blank ...
Страница 76: ...Piping Liebert CW System Design Manual 66 Page intentionally left blank ...
Страница 90: ...Electrical Field Connections Liebert CW System Design Manual 80 Page intentionally left blank ...
Страница 114: ...Optional Liebert Air Economizer for Liebert CW Liebert CW System Design Manual 104 Page intentionally left blank ...