Liebert CW System Data
Liebert
®
CW
™
System Design Manual
16
HUMIDIFIER SECTION
Infrared Humidifier Note (50Hz Models are 22.1 lb/h (10.0 kg/h); 9.6 kW)
Capacity, lb/hr (kg/h)
22.1 (10)
22.1 (10)
22.1 (10)
—
—
kW
9.6
9.6
9.6
9.6
—
—
Steam Generating Humidifier (Water Conductivity between 200-500 micro-ohms is required for ideal operation) - Not applicable to units with EC
fans.
Capacity, lb/hr (kg/h)
22 (10.0)
22 (10.0)
—
—
—
—
kW
9.6
9.6
—
—
—
—
FILTER SECTION
Disposable Type - Nominal Size and Quantities, MERV8 and MERV11 (option)
Downflow Models
Nominal Size, in
24 x 31
21.5 x 24
29.5 x 28.5
Quantity
5
5
10
10
12
12
Upflow Models (Front Return)
Nominal Size, in
18 x 24
N/A
N/A
N/A
N/A
Quantity
2
2
N/A
N/A
N/A
N/A
Upflow Models (Bottom & Rear Return)
Nominal Size, in
18 x 24
N/A
N/A
N/A
N/A
Quantity
10
10
N/A
N/A
N/A
N/A
CONNECTION SIZES
Chilled Water, OD Copper
2-1/8”
2-5/8”
3-1/8”
3-1/8”
3-1/8”
(qty 2)
3-1/8”
(qty 2)
Infrared Humidifier, OD Copper
1/4”
1/4”
1/4”
1/4”
N/A
N/A
Condensate Drain, FPT
1-1/4”
1-1/4”
1-1/4”
1-1/4”
1-1/4”
1-1/4”
Steam Reheat, MPT
3/4”
3/4”
N/A
N/A
N/A
N/A
Hot Water Reheat, OD Copper
7/8”
7/8”
N/A
N/A
N/A
N/A
Steam Humidifier, MPT
1/2”
1/2”
N/A
N/A
N/A
N/A
Table 2-7
Physical data—Liebert CW106 - CW400, 50/60Hz models (continued)
Model Sizes
106
114
146
181
300
400
Содержание CW089
Страница 2: ......
Страница 8: ...Liebert CW System Design Manual vi ...
Страница 10: ...Liebert CW System Design Manual vi Page intentionally left blank ...
Страница 18: ...Nomenclature and Components Liebert CW System Design Manual 8 Page intentionally left blank ...
Страница 62: ...Dimensions Liebert CW System Design Manual 52 Page intentionally left blank ...
Страница 76: ...Piping Liebert CW System Design Manual 66 Page intentionally left blank ...
Страница 90: ...Electrical Field Connections Liebert CW System Design Manual 80 Page intentionally left blank ...
Страница 114: ...Optional Liebert Air Economizer for Liebert CW Liebert CW System Design Manual 104 Page intentionally left blank ...