Piping Connections—Downflow Models with EC Fans
59
Liebert
®
CW
™
System Design Manual
Figure 5-7 Primary connection locations, downflow, CW089, CW106 and CW114 with EC fans
Point
Description
X, in. (mm)
Y, in. (mm)
Connection Size / Opening
CD
Condensate Drain *
103-1/2 (2629)
28 (711)
1-1/4” FPT
w/ Optional Pump
103-1/2 (2629)
28 (711)
1/2” Cu Sweat
HUM
Humidifier Supply Line
107-1/2 (2731)
29 (737)
1/4” Cu Sweat
CWS 2
2-Way Chilled Water Supply
118-1/2 (3010)
31 (787)
CW106: 2-1/8”; CW089, CW114: 2-5/8”
CWS 3
3-Way Chilled Water Supply
115-1/2 (2934)
31 (787)
CW106: 2-1/8”; CW089, CW114: 2-5/8”
CWR 2
2-Way Chilled Water Return
112-1/2 (2858)
31 (787)
CW106: 2-1/8”; CW089, CW114: 2-5/8”
CWR 3
3-Way Chilled Water Return
115-1/2 (2934)
22 (559)
CW106: 2-1/8”; CW089, CW114: 2-5/8”
E1
Electrical Connection (High Volt)
35 (889)
31 (787)
2"
E2
Electrical Connection (High Volt)
34 (864)
29 (737)
2"
LV1
Electrical Connection (Low Volt)
35-1/2 (902)
26-1/2 (673)
1-3/8”
LV2
Electrical Connection (Low Volt)
33-1/2 (851)
26-1/2 (673)
1-3/8”
B
Blower Outlet
4 (102)
33 (838)
94 x 31 (2388mm x 787mm)
*
Field-pitch condensate drain line a minimum of 1/8” (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap.
Do not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must
comply with all local codes.
FRONT OF UNIT
FRONT VIEW
SECTION A-A
NOTE: Drawing not to scale.
Tolerance on
all piping dimensions
is ± 1/2" (13mm).
ALL DIMENSIONS FROM
REAR CORNER OF UNIT
INCLUDING PANELS
122"
3099mm
35"
889mm
28 1/16"
712mm
TYPICAL
AIR DISCHARGE
AREA
31"
787mm
TYPICAL
AIR DISCHARGE
AREA
CWS 2
CWS 3
B
Y
X
O
LV1
LV2
E1
E2
HUM
CD
CWR 2
CWR 3
DPN001628
Rev. 5
A
A
Содержание CW089
Страница 2: ......
Страница 8: ...Liebert CW System Design Manual vi ...
Страница 10: ...Liebert CW System Design Manual vi Page intentionally left blank ...
Страница 18: ...Nomenclature and Components Liebert CW System Design Manual 8 Page intentionally left blank ...
Страница 62: ...Dimensions Liebert CW System Design Manual 52 Page intentionally left blank ...
Страница 76: ...Piping Liebert CW System Design Manual 66 Page intentionally left blank ...
Страница 90: ...Electrical Field Connections Liebert CW System Design Manual 80 Page intentionally left blank ...
Страница 114: ...Optional Liebert Air Economizer for Liebert CW Liebert CW System Design Manual 104 Page intentionally left blank ...