Electrical Field Connections—Upflow Models
75
Liebert
®
CW
™
System Design Manual
Figure 6-7 Electrical field connections (low voltage), upflow, CW026 – CW084
NOTE: REFER TO SPECIFICATION SHEET FOR FULL LOAD
AMP. AND WIRE SIZE AMP. RATINGS
3 7
3 8
2 4
5 0
9 1
9 2
9 3
5 1
5 5
5 6
Intellislot Housings.
Optional Monitoring and
Communication cards inserted here.
Smoke detector alarm connections.
are #91-comm., #92-NO, and #93-NC.
terminals from optional smoke detector
remote alarm circuits. Factory wired
Field supplied 24V. Class 2 wire to
Factory Wiring
Back of Electric Box
Back of Unit
Underside of Unit Top
7 5
7 6
9 4
9 5
9 6
9 7
Common Alarm Connections.
Field supplied 24V. Class 2
wiring to common alarm
terminals 75 + 76 which are
factory connected to common
alarm relay (R3). Optional
extra common alarm terminals
94+95 and 96+97 are also
connected to R3 relay.
24V. Class 2 wire for special alarms.
Field supplied
Special alarm connections.
Remote unit shutdown.
field supplied 24V Class 2 wire.
having a minimum 50VA rating. Use
37 + 38 with normally closed switch
jumper between terminals
Replace existing
DPN003201
Pg. 1 Rev. 1
Содержание CW089
Страница 2: ......
Страница 8: ...Liebert CW System Design Manual vi ...
Страница 10: ...Liebert CW System Design Manual vi Page intentionally left blank ...
Страница 18: ...Nomenclature and Components Liebert CW System Design Manual 8 Page intentionally left blank ...
Страница 62: ...Dimensions Liebert CW System Design Manual 52 Page intentionally left blank ...
Страница 76: ...Piping Liebert CW System Design Manual 66 Page intentionally left blank ...
Страница 90: ...Electrical Field Connections Liebert CW System Design Manual 80 Page intentionally left blank ...
Страница 114: ...Optional Liebert Air Economizer for Liebert CW Liebert CW System Design Manual 104 Page intentionally left blank ...