![Emerson CW089 Скачать руководство пользователя страница 67](http://html.mh-extra.com/html/emerson/cw089/cw089_design-manual_101149067.webp)
Piping Connections—Downflow Models with EC Fans
57
Liebert
®
CW
™
System Design Manual
Figure 5-5 Primary connection locations, downflow, CW051 and CW060 with EC fans
Point
Description
X, in (mm)
Y, in (mm)
Connection Size / Opening, in (mm)
CD
Condensate Drain*
61 (1550)
27-3/4 (705)
3/4 (19) FPT
w/Optional Condensate Pump**
1/2 (13) Cu Sweat
HUM
Humidifier Supply Line
58-3/8 (1484)
31-7/16 (799)
1/4 (6) Cu Sweat
CWP
Chilled Water Piping Slot (Center)
66-1/2 (1690)
31-1/4 (794)
11 x 3 (279 x 76)
Supply & Return Piping Diameter
—
—
CW051: 1-5/8 (41)
CW060: 2-1/8 (54)
HV
High Volt Electrical Connection
59-1/2 (1512)
29-3/4 (756)
3 (76)
LV
Low Volt Electrical Connection
59-1/2 (1512)
32 (813)
7/8 (22)
B
Blower Outlet Opening
4 (101)
33 (838)
51 x 31 (1295) x 787)
*
Field pitch Condensate Drain line a minimum of 1/8” (3.2 mm) per foot (305 mm). All units contain a factory installed condensate trap. Do
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.
** Optional Condensate Pump to be field installed under unit.
FRONT VIEW
NOTE: Drawing not to scale.
Tolerance on
all piping locating
dimensions
± 1/2" (13mm).
FRONT OF UNIT
SECTION A-A
X
Y
ALL DIMENSIONS FROM
RIGHT REAR CORNER OF UNIT
WITH PANELS ASSEMBLED
0
CD
LV
HV
CWP
35"
889mm
74"
1880mm
31"
787mm
TYPICAL AIR
DISCHARGE AREA
24 1/4"
615mm
AIR DISCHARGE
AREA
24 1/2"
623mm
AIR DISCHARGE
AREA
B
HUM
DPN002035
Rev. 2
A
A
Содержание CW089
Страница 2: ......
Страница 8: ...Liebert CW System Design Manual vi ...
Страница 10: ...Liebert CW System Design Manual vi Page intentionally left blank ...
Страница 18: ...Nomenclature and Components Liebert CW System Design Manual 8 Page intentionally left blank ...
Страница 62: ...Dimensions Liebert CW System Design Manual 52 Page intentionally left blank ...
Страница 76: ...Piping Liebert CW System Design Manual 66 Page intentionally left blank ...
Страница 90: ...Electrical Field Connections Liebert CW System Design Manual 80 Page intentionally left blank ...
Страница 114: ...Optional Liebert Air Economizer for Liebert CW Liebert CW System Design Manual 104 Page intentionally left blank ...