Piping
Liebert
®
CW
™
System Design Manual
60
Figure 5-8 Primary connection locations, downflow, CW146 and CW181 with EC fans
Point
Description
X
In. (mm)
Y
In. (mm)
Connection Size / Opening
CD
Condensate Drain *
110 (2794)
35 (889)
1-1/4” FPT
w/ Optional Pump
110 (2794)
35 (889)
1/2” Cu Sweat
HUM
Humidifier Supply Line
101 (2565)
43 (1092)
1/4” Cu Sweat
CWS
2-Way Chilled Water Supply
117 (2972)
37 (940)
3-1/8”
3-Way Chilled Water Supply
117 (2972)
37 (940)
3-1/8”
CWR
2-Way Chilled Water Return
117 (2972)
30 (762)
3-1/8”
3-Way Chilled Water Return
117 (2972)
30 (762)
3-1/8”
E1
Electrical Conn. (High Volt)
113 (2870)
43 (1092)
2"
E2
Electrical Conn. (High Volt)
110 (2794)
43 (1092)
2"
LV1
Electrical Conn. (Low Volt)
2-1/2 (64)
36 (914)
7/8”
LV2
Electrical Conn. (Low Volt)
2-1/2 (64)
37-1/2 (953)
7/8”
LV3
Electrical Conn. (Low Volt)
2-1/2 (64)
39 (991)
7/8”
B
Blower Outlet
4-1/2 (114)
44 (1118)
93" x 41" (2362 mm x 1041 mm)
*
Field-pitch condensate drain line a minimum of 1/8” (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.
FRONT OF UNIT
FRONT VIEW
SECTION A-A
NOTE: Drawing not to scale.
Tolerance on
all piping dimensions
is ± 1/2" (13mm).
ALL DIMENSIONS FROM
REAR CORNER OF UNIT
INCLUDING PANELS
E2
HUM
CD
B
LV1
LV2
O
X
Y
A
A
CWS
CWR
41"
1041mm
TYP
AIR DISCHARGE
AREA
47"
1194mm
122"
3099mm
LV3
E1
29 3/8"
746mm
TYP
AIR DISCHARGE
AREA
DPN001693
Rev. 2
Содержание CW089
Страница 2: ......
Страница 8: ...Liebert CW System Design Manual vi ...
Страница 10: ...Liebert CW System Design Manual vi Page intentionally left blank ...
Страница 18: ...Nomenclature and Components Liebert CW System Design Manual 8 Page intentionally left blank ...
Страница 62: ...Dimensions Liebert CW System Design Manual 52 Page intentionally left blank ...
Страница 76: ...Piping Liebert CW System Design Manual 66 Page intentionally left blank ...
Страница 90: ...Electrical Field Connections Liebert CW System Design Manual 80 Page intentionally left blank ...
Страница 114: ...Optional Liebert Air Economizer for Liebert CW Liebert CW System Design Manual 104 Page intentionally left blank ...