Optional Configuration for Liebert CW Seismic Application
Liebert
®
CW
™
System Design Manual
88
Figure A-4 IBC-certified seismic floor stand data, downflow, CW026 – CW114 with EC fans
Dimensional Data, in. (mm)
Model
Overall Unit Width
A
B
CW026, CW038, CW041
50 (1270)
48 (1219)
33 (838)
CW051, CW060
74 (1880)
72 (1829)
CW076, CW084
99 (2515)
97 (2464)
CW89, CW106, CW114
120 (3048)
118 (2997)
JACK
* Foot provides ±1.5" (38mm)
adjustment from nominal height H
Foot Detail
4.6"
117mm
*
A
B
H
18.4"
467mm
NOTE:
1. The floor stand used with EC units is not symmetrical and its orientation to the Liebert CW is critical to lowering the EC fans.
Unless the floor stand is installed in the correct position, the blowers will not lower into the floor stand.
2. Not applicable to 24" & 30" tall floorstands.
2
DPN003209
Pg. 6 Rev. 2