Liebert CW System Data
Liebert
®
CW
™
System Design Manual
12
Table 2-4
Motor size required to deliver rated airflow, models with forward-curved blowers
External Static
Pressure
0.2"
0.4"
0.6"
0.8"
1.0"
1.2"
1.4"
Model
Rated Airflow
CFM (l/s)
Motor Size, hp
026
5050 (2383)
3
5
5
5
5
5
5
038
5850 (2761)
5
5
5
—
—
—
041
5750 (2714)
5
—
—
—
—
—
—
051
9150 (4318)
7.5
7.5
—
—
—
—
—
060
8900 (4200)
7.5
7.5
—
—
—
—
—
076
12100 (5711)
10
15
15
15
15
—
—
084
11650 (5498)
10
15
15
15
15
—
—
106
17100 (8070)
15
15
15
15
15
—
—
114
16500 (7787)
15
15
15
15
—
—
—
*
Delivered airflow is less than rated airflow
Table 2-5
Maximum airflow with maximum motor size at listed static pressure,
models with forward-curved blowers
External Static
Pressure
0.2"
0.4"
0.6"
0.8"
1.0"
1.2"
1.4"
Model
Rated
Airflow
CFM (l/s)
Airflow, CFM (l/s)
026
5050
(2383)
5050
(2383)
5050
(2383)
5050
(2383)
5050
(2383)
5050
(2383)
5050
(2383)
5050
(2383)
038
5850
(2761)
5850
(2761)
5850
(2761)
5850
(2761)
5750
(2714)
5600
(2643)
5450
(2572)
5350
(2525)
041
5750
(2714)
5750
(2714)
5750
(2714)
5600
(2643)
5450
(2572)
5350
(2525)
—
—
051
9150
(4318)
9150
(4318)
9150
(4318)
9100
(4295)
8900
(4200)
8700
(4106)
8550
(4035)
8350
(3941)
060
8900
(4200)
8900
(4200)
8900
(4200)
8750
(4130)
8550
(4035)
8400
(3964)
8200
(3870)
8050
(3799)
076
12100
(5711)
12100
(5711)
12100
(5711)
12100
(5711)
12100
(5711)
12100
(5711)
11600
(5475)
11000
(5191)
084
11650
(5498)
11650
(5498)
11650
(5498)
11650
(5498)
11650
(5498)
11650
(5498)
11400
(5380)
NA
106
17100
(8070)
17100
(8070)
17100
(8070)
17100
(8070)
17100
(8070)
17100
(8070)
16400
(7740)
16100
(7598)
114
16500
(7787)
16500
(7787)
16500
(7787)
16500
(7787)
16500
(7787)
16100
—
—
Содержание CW089
Страница 2: ......
Страница 8: ...Liebert CW System Design Manual vi ...
Страница 10: ...Liebert CW System Design Manual vi Page intentionally left blank ...
Страница 18: ...Nomenclature and Components Liebert CW System Design Manual 8 Page intentionally left blank ...
Страница 62: ...Dimensions Liebert CW System Design Manual 52 Page intentionally left blank ...
Страница 76: ...Piping Liebert CW System Design Manual 66 Page intentionally left blank ...
Страница 90: ...Electrical Field Connections Liebert CW System Design Manual 80 Page intentionally left blank ...
Страница 114: ...Optional Liebert Air Economizer for Liebert CW Liebert CW System Design Manual 104 Page intentionally left blank ...