11
Liebert
®
CW
™
System Design Manual
Table 2-3
Performance data for select Liebert CW Units with EC fans, High Delta T conditions
Entering
Water
Liebert CW Model
Numbers
CW106
CW114
CW146
CW181
CW300
CW400
CAPACITY DATA BTU/HR (KW) BASED ON 50°F (10°C) ENTERING WATER, 0.2" ESP WITH ASHRAE 127-2012 STANDARD
Return Air Conditions of 80°F DB, 62.8°F WB, 52.3°F Dew Point (26.6°C DB, 17.1°C WB) 38.1% RH
14°F (7.8°C)
Water Rise
Total, kBTUH (kW)
301.6 (88.3)
376.7 (110.3)
439.2 (128.6)
588.8 (172.4)
797.1 (233.4) 1054.6 (308.8)
Sensible, kBTUH (kW)
301.6 (88.3)
376.7 (110.3)
439.2 (128.6)
588.8 (172.4)
797.1 (233.4) 1054.6 (308.8)
Flow Rate, GPM (l/s)
46.6 (2.9)
58.0 (3.7)
66.1 (4.2)
89.3 (5.6)
120.8 (7.6)
161.6 (10.2)
Press. Drop, ft (kPa)
7.8 (23.3)
14.0 (41.8)
4.2 (12.6)
9.4 (28.1)
3.6 (10.8)
7.9 (23.6)
16°F (8.9°C)
Water Rise
Total, kBTUH (kW)
273.9 (80.2)
353.5 (103.5)
405.0 (118.6)
560.1 (164.0)
733.2 (214.7) 1004.7 (294.2)
Sensible, kBTUH (kW)
273.9 (80.2)
353.5 (103.5)
405.0 (118.6)
560.1 (164.0)
733.2 (214.7) 1004.7 (294.2)
Flow Rate, GPM (l/s)
37.4 (2.4)
47.8 (3.0)
53.6 (3.4)
74.6 (4.7)
97.8 (6.2)
135.1 (8.5)
Press. Drop, ft (kPa)
5.2 (15.5)
9.8 (29.3)
2.9 (8.7)
6.8 (20.3)
2.4 (7.2)
5.7 (17.0)
CAPACITY DATA BTU/HR (KW) BASED ON 50°F (10°C) ENTERING WATER, 0.2" ESP WITH ASHRAE 127-2012 STANDARD
Return Air Conditions of 85°F DB, 64.5°F WB, 52.3°F Dew Point (29.4°C DB, 18.1°C WB) 32.4% RH
14°F (7.8°C)
Water Rise
Total, kBTUH (kW)
383.9 (112.4)
466.2 (136.5)
548.8 (160.7)
717.2 (210.0)
998.9 (292.5) 1284.8 (376.2)
Sensible, kBTUH (kW)
383.9 (112.4)
466.2 (136.5)
548.8 (160.7)
717.2 (210.0)
998.9 (292.5) 1284.8 (376.2)
Flow Rate, GPM (l/s)
58.3 (3.7)
70.7 (4.5)
81.8 (5.2)
107.6 (6.8)
149.5 (9.4)
194.4 (12.3)
Press. Drop, ft (kPa)
11.9 (35.6)
20.1 (60.1)
6.2 (18.5)
13.2 (39.5)
5.3 (15.8)
11.0 (32.9)
16°F (8.9°C)
Water Rise
Total, kBTUH (kW)
359.3 (105.2)
446.0 (130.6)
519.4 (152.1)
692.9 (202.9)
944.3 (276.5) 1242.8 (363.9)
Sensible, kBTUH (kW)
359.3 (105.2)
446.0 (130.6)
519.4 (152.1)
692.9 (202.9)
944.3 (276.5) 1242.8 (363.9)
Flow Rate, GPM (l/s)
48.0 (3.0)
59.3 (3.7)
67.9 (4.3)
91.1 (5.7)
124.1 (7.8)
164.9 (10.4)
Press. Drop, ft (kPa)
8.3 (24.8)
14.5 (43.3)
4.4 (13.2)
9.8 (29.3)
3.7 (11.1)
8.1 (24.2)
CAPACITY DATA BTU/HR (KW) BASED ON 50°F (10°C) ENTERING WATER, 0.2" ESP WITH ASHRAE 127-2012 STANDARD
Return Air Conditions of 90°F DB, 66.1°F WB, 52.3°F Dew Point (32.2°C DB, 18.9°C WB) 27.6% RH
14°F (7.8°C)
Water Rise
Total, kBTUH (kW)
463.1 (135.6)
552.2 (161.7)
654.0 (191.5)
840.5 (246.1) 1192.9 (349.3) 1506.1 (441.0)
Sensible, kBTUH (kW)
463.1 (135.6)
552.2 (161.7)
654.0 (191.5)
840.5 (246.1) 1192.9 (349.3) 1506.1 (441.0)
Flow Rate, GPM (l/s)
69.6 (4.4)
83.0 (5.2)
96.7 (6.1)
125.1 (7.9)
177.1 (11.2)
225.8 (14.2)
Press. Drop,- ft (kPa)
16.5 (49.3)
27.0 (80.7)
8.5 (25.4)
17.4 (52.0)
7.2 (21.5)
14.5 (43.3)
16°F (8.9°C)
Water Rise
Total, kBTUH (kW)
440.6 (129.0)
533.8 (156.3)
627.4 (183.7)
819.3 (239.9) 1142.7 (334.6) 1469.9 (430.4)
Sensible, kBTUH (kW)
440.6 (129.0)
533.8 (156.3)
627.4 (183.7)
819.3 (239.9) 1142.7 (334.6) 1469.9 (430.4)
Flow Rate, GPM (l/s)
58.1 (3.7)
70.3 (4.4)
81.3 (5.1)
106.9 (6.7)
148.8 (9.4)
193.1 (12.2)
Press. Drop, ft (kPa)
11.7 (35.0)
19.8 (59.2)
6.1 (18.2)
13.0 (38.9)
5.2 (15.5)
10.8 (32.3)
Содержание CW089
Страница 2: ......
Страница 8: ...Liebert CW System Design Manual vi ...
Страница 10: ...Liebert CW System Design Manual vi Page intentionally left blank ...
Страница 18: ...Nomenclature and Components Liebert CW System Design Manual 8 Page intentionally left blank ...
Страница 62: ...Dimensions Liebert CW System Design Manual 52 Page intentionally left blank ...
Страница 76: ...Piping Liebert CW System Design Manual 66 Page intentionally left blank ...
Страница 90: ...Electrical Field Connections Liebert CW System Design Manual 80 Page intentionally left blank ...
Страница 114: ...Optional Liebert Air Economizer for Liebert CW Liebert CW System Design Manual 104 Page intentionally left blank ...