Electrical Data
Liebert
®
CW
™
System Design Manual
20
Table 3-3
Indoor evaporator fan motor electrical requirements—60Hz systems
Hp
208
230
460
575
FLA
LRA
FLA
LRA
FLA
LRA
FLA
LRA
2.0
7.5
46.9
6.8
40.8
3.4
20.4
2.7
16.2
3.0
10.6
66.0
9.6
58.0
4.8
26.8
3.9
23.4
5.0
16.7
105.0
15.2
91.0
7.6
45.6
6.1
36.6
7.5
24.2
152.0
22.0
132.0
11.0
66.0
9.0
54.0
10.0
30.8
193.0
28.0
168.0
14.0
84.0
11.0
66.0
15.0
46.2
290.0
42.0
252.0
21.0
126.0
17.0
102.0
20.0
59.4
321.0
54.0
290.0
27.0
145.0
22.0
116.0
1.
Refer to General Data Section for standard fan motor size on units.
2.
FLA = Full Load Amps (does not reflect typical operating amps)
WSA = Wire Sizing Amps (Minimum supply circuit ampacity)
MFCB = Maximum Fuse or Circuit Breaker Size
3.
Amperage requirements are based on the rated max FLA current of each component in the unit. The rated
max FLA current of the unit is not the sum total of all components, but is the total of the components which
operate during maximum electrical load conditions.
4.
The values in the chart are for power of the unit only.
5.
Units are 3 phase, 60 cycle.
6.
For units with other variations not listed above, consult your Emerson representative for electrical
requirements.
7.
SCCR - Short Circuit Current Rating 65,000 rms (less than 480V), 25,000 rms (575V).
Содержание CW089
Страница 2: ......
Страница 8: ...Liebert CW System Design Manual vi ...
Страница 10: ...Liebert CW System Design Manual vi Page intentionally left blank ...
Страница 18: ...Nomenclature and Components Liebert CW System Design Manual 8 Page intentionally left blank ...
Страница 62: ...Dimensions Liebert CW System Design Manual 52 Page intentionally left blank ...
Страница 76: ...Piping Liebert CW System Design Manual 66 Page intentionally left blank ...
Страница 90: ...Electrical Field Connections Liebert CW System Design Manual 80 Page intentionally left blank ...
Страница 114: ...Optional Liebert Air Economizer for Liebert CW Liebert CW System Design Manual 104 Page intentionally left blank ...