4.5 Cabinet and Floor-planning Dimensions—
Upflow Models with Forward-curved Blowers
Figure 4-15 Cabinet and Floor-planning dimensions, upflow, CW026 – CW084 with forward-curved blowers
Chilled
Water
Model
Dimensional Data inches (mm)
Net
Weight
lb (kg)
No. of
Blowers
A
B
C
D
E
F
G
H
J
K
L
M
CW026
1
50
(1270)
48
(1219)
46
(1168)
44
(1118)
3 (76)
5 (127)
18
(457)
15-7/8
(403)
18-5/8
(473)
1 (25)
19-1/2
(495)
N/A
760
(345)
CW038
795
(361)
CW041
855
(388)
CW051
2
74
(1880)
72
(1289)
70
(1778)
68
(1727)
4 (102)
20
(508)
14-3/4
(375)
11
(279)
1090
(494)
CW060
1155
(524)
CW076
99
(2515)
97
(2464)
95
(2413)
86
(2184)
6.5
(165)
5 (127)
18
(457)
18-5/8
(473)
2 (51)
12-5/8
(321)
1320
(599)
CW084
1420
(644)
MODELS W/ REAR RETURN
A
OVERALL
35.00"
889mm
CABINET
72.00"
1829mm
33.00"
838mm
UNIT BASE
B
UNIT BASE
D
AIR RETURN
F
G
AIR
RETURN
BOTTOM AIR RETURN OPENING CW026-CW084
C
31.00"
787mm
B
33.00"
838mm
E
Notes:
1. Air Grille may be supplied on units with front or rear return air.
2. Shaded areas indicate a recommended clearance of 36" (914mm)
be provided for component access and filter removal.
3. A Return Air Grille may be ordered in place of the duct flange on
units with rear return air (see specification sheet for option supplied).
1.00"
25mm
TYP.
1" (25mm) duct flange
for plenum alignment
FLANGES PROVIDED ON
BLOWER(S) OUTLET FOR
SUPPLY AIR DUCTING.
CW026-041
J
L
CW051-084
H
Typ.
J
Typ.
M
L
K
K
Front of unit
Front of unit
H
DPN003194
Rev. 2
Содержание CW089
Страница 2: ......
Страница 8: ...Liebert CW System Design Manual vi ...
Страница 10: ...Liebert CW System Design Manual vi Page intentionally left blank ...
Страница 18: ...Nomenclature and Components Liebert CW System Design Manual 8 Page intentionally left blank ...
Страница 62: ...Dimensions Liebert CW System Design Manual 52 Page intentionally left blank ...
Страница 76: ...Piping Liebert CW System Design Manual 66 Page intentionally left blank ...
Страница 90: ...Electrical Field Connections Liebert CW System Design Manual 80 Page intentionally left blank ...
Страница 114: ...Optional Liebert Air Economizer for Liebert CW Liebert CW System Design Manual 104 Page intentionally left blank ...