Floor-stand Dimensions—Units with EC Fans
43
Liebert
®
CW
™
System Design Manual
Figure 4-20 Floor-stand and floor-planning dimensions, downflow,
CW089, CW106 and CW114 with EC fans
Piping access
area
NOTE:
1. This floor stand should be used when EC fans are intended to be lowered into
the floor stand. The standard Liebert CW floor stand can be used “if” the fans are to
remain in their original raised position.
2. All paneled sides of unit overhang floorstand 1” (25mm).
3. The floor stand used with EC units is not symmetrical and its orientation to the
Liebert CW is critical for lowering the EC fans. Unless the floor stand is installed in
the correct position, the blowers will not lower into the floor stand.
4. Jack and jack support are shipped loose and are intended to be placed into position
under each fan and utilized to lower or raise that fan as needed.
5. Does not apply to 24" high floorstand.
*Leveling feet are provided with 1-1/2” (38mm) adjustment from nominal height “A”.
See note 4
SUPPORT FEET CENTERS
20 1/4"
514mm
1"
25mm
3/4"
19mm
31 1/2"
800mm
CENTER FEET
3/4"
19mm
59 1/4"
1505mm
118 1/2"
3010mm
3/4"
19mm
120"
3048mm
7/8"
23mm
3"
76mm
TYP.
121 1/2"
3086mm
OVERALL
32"
813mm
CENTER FEET
TYP. (2) PLACES
33"
838mm
1"
25mm
A*
19 1/4"
489mm
35"
889mm
OVERALL
5
DPN003191
Rev. 1
Height,
in. (mm)
A*
24 (610)
30 (762)
36 (914)
42 (1067)
48 (1219)
Содержание CW089
Страница 2: ......
Страница 8: ...Liebert CW System Design Manual vi ...
Страница 10: ...Liebert CW System Design Manual vi Page intentionally left blank ...
Страница 18: ...Nomenclature and Components Liebert CW System Design Manual 8 Page intentionally left blank ...
Страница 62: ...Dimensions Liebert CW System Design Manual 52 Page intentionally left blank ...
Страница 76: ...Piping Liebert CW System Design Manual 66 Page intentionally left blank ...
Страница 90: ...Electrical Field Connections Liebert CW System Design Manual 80 Page intentionally left blank ...
Страница 114: ...Optional Liebert Air Economizer for Liebert CW Liebert CW System Design Manual 104 Page intentionally left blank ...