9
Liebert
®
CW
™
System Design Manual
2.0
Liebert CW System Data
Table 2-1
Performance data, CW026-CW400, 50/60Hz, upflow and downflow models with EC fans
Model No.
026
038
041
051
060
076
084
089 *
106
114
146 *
181 *
300 *
400 *
CAPACITY DATA BTU/H (KW) BASED ON 45°F (7.2°C) ENTERING WATER, 10°F (5.5°C) WATER RISE
75°F DB, 61°F WB (23.9°C DB, 16.1°C WB) 45% RH
Total Capacity, kBTUH (kW)
83.2
(24.4)
115.3
(33.8)
152.7
(44.7)
175.3
(51.4)
231.5
(67.80)
240.6
(70.50)
297.2
(87.1)
347.1
(101.7)
358.4
(105.0)
448.8
(131.5)
522.9
(153.2)
720.1
(211)
1003.0
(293.90)
1390.0
(407.3)
Sensible Capacity, kBTUH (kW)
83.2
(24.4)
113.1
(33.1)
136.6
(40.0)
173.6
(50.9)
205.5
(60.2)
230.3
(67.50)
264.7
77.60)
295.5
(86.6)
336.8
(98.7)
393.5
(115.3)
472.5
(138.4)
604.6
(177.1)
911.4
(267.0)
1163.0
(340.8)
Flow Rate, GPM (l/s)
17.6
(1.1)
24.6
(1.6)
32.3
(2.0)
37.8
(2.4)
49.4
(3.1)
51.6
(3.3)
63.1
(4.0)
72.5
(4.6)
76.6
(4.8)
95.5
(6.0)
109.2
(6.9)
151.1
(9.5)
209.9
(13.2)
292.6
(18.5)
Pressure Drop, ft (kPA)
11.8
(35.2)
18.1
(54.2)
16.4
(49.0)
9.3
(28.0)
10.2
(30.5)
10.3
(30.7)
17.9
(53.5)
21.6
(64.5)
20.1
(60.1)
35.8
(106.9)
10.9
(32.5)
25.2
(75.3)
10.1
(30.2)
23.8
(71.0)
80°F DB, 62.8°F WB (26.7°C DB, 17.1°C WB) 38% RH
Total Capacity, kBTUH (kW) 105.5
(30.9)
143.0
(41.9)
183.8
(53.9)
219.6
(64.3)
279.5
(81.9)
297.2
(87.1)
357.6
(104.8)
411.9
(120.70)
438.0
(128.3)
537.3
(157.4)
630.3
(184.7)
850.1
(249.1)
1211.0
(354.8)
1641.0
(480.8)
Sensible Capacity, kBTUH (kW) 105.5
(30.9)
140.4
(41.1)
166.6
(48.8)
217.3
(63.7)
251.1
(73.6)
285.5
(83.7)
322.7
(94.6)
356.9
(104.6)
414.6
(121.5)
478.6
(140.2)
575.6
(168.7)
728.4
(213.4)
1112.0
(325.8)
1402.0
(410.8)
Flow Rate, GPM (l/s)
22.1
(1.4)
30.1
(1.9)
38.5
(2.4)
46.6
(2.9)
59
(3.7)
62.9
(4.0)
75.1
(4.70)
85.4
(5.4)
92.4
(5.8)
113.1
(7.1)
130.6
(8.2)
177
(11.2)
251.3
(15.9)
342.6
(21.6)
Pressure Drop, ft (kPA)
18.0
(53.7)
26.7
(79.7)
22.6
(67.5)
13.8
(41.4)
14.1
(42.2)
14.8
(44.2)
24.6
(73.6)
29.2
(87.1)
28.5
(85.1)
48.9
(146)
15.1
(45.2)
33.7
(100.6)
14.1
(42.0)
31.7
(94.8)
85°F DB, 64.5°F WB (29.4°C DB, 18.1°C WB) 32.3% RH
Total Capacity, kBTUH (kW) 127.2
(37.3)
169.9
(49.8)
213.9
(62.7)
262.4
(76.9)
325.7
(95.4)
352.1
(103.2)
415.9
(121.9)
474.1
(138.9)
515.4
(151)
622.5
(182.4)
733.9
(215.0)
974.9
(285.6)
1412.0
(413.7)
1881.0
(551.1)
Sensible Capacity, kBTUH (kW) 127.2
(37.3)
167.2
(49.0)
195.7
(57.3)
259.8
(76.1)
295.4
(86.6)
339.4
(99.4)
379.2
(111.1)
416.6
(122.1)
490.9
(143.8)
561.4
(164.5)
676.1
(198.1)
848.8
(248.7)
1307.0
(383.0)
1634.0
(478.8)
Flow Rate, GPM (l/s)
26.4
(1.7)
35.5
(2.2)
44.5
(2.8)
55.2
(3.5)
68.2
(4.3)
73.9
(4.7)
86.7
(5.5)
97.8
(6.2)
107.9
(6.8)
130.1
(8.2)
151.2
(9.5)
201.9
(12.7)
291.4
(18.4)
390.6
(24.6)
Pressure Drop, ft (kPA)
25.1
(75.2)
36.5
(109.1)
29.4
(87.8)
19.0
(56.8)
18.4
(55.0)
19.9
(59.4)
32.1
(95.8)
37.4
(111.8)
38.0
(113.4)
63.3
(189.2)
19.8
(59.2)
42.9
(128.1)
18.5
(55.2)
40.3
(120.5)
CAPACITY DATA BTU/H (KW) BASED ON 50°F (10°C) ENTERING WATER, 12°F (6.66°C) WATER RISE
75°F DB, 61°F WB (23.9°C DB, 16.1°C WB) 45% RH
Total Capacity, kBTUH (kW)
46.5
(13.6)
75.3
(22.1)
102.3
(30.0)
108.3
(31.7)
152.9
(44.8)
156.5
(45.9)
198.7
(58.2)
230.1
(67.4)
238.5
(69.9)
300.4
(88.0)
351.3
(102.9)
478.1
(140.1)
672.7
(197.1)
920.3
(269.6)
Sensible Capacity, kBTUH (kW)
46.5
(13.6)
75.3
(22.1)
102.3
(30)
108.3
(31.7)
152.9
(44.8)
156.5
(45.9)
198.7
(58.2)
230.1
(67.4)
238.5
(69.9)
300.4
(88)
351.3
(102.9)
478.1
(140.1)
672.7
(197.1)
920.3
(269.6)
Flow Rate, GPM (l/s)
8.6
(0.5)
13.9
(0.9)
18.5
(1.2)
20.4
(1.3)
28.2
(1.8)
29.1
(1.8)
36.3
(2.3)
41.0
(2.6)
43.9
(2.8)
55.0
(3.5)
62.6
(4.0)
85.8
(5.4)
120.1
(7.6)
166.1
(10.5)
Pressure Drop, ft (kPA)
3.0
(9.0)
6.0
(17.9)
5.9
(17.6)
2.9
(8.6)
3.6
(10.7)
3.5
(10.5)
6.4
(19.1)
7.5
(22.4)
7.1
(21.2)
12.7
(38.0)
3.8
(11.5)
8.8
(26.4)
3.5
(10.6)
8.3
(24.8)
80°F DB, 62.8°F WB (26.7°C DB, 17.1°C WB) 38% RH
Total Capacity, kBTUH (kW)
74.5
(21.8)
104.7
(30.7)
134
(39.3)
158.6
(46.5)
202.3
(59.3)
215.5
(63.1)
260.2
(76.2)
294.9
(86.4)
320.4
(93.9)
389.4
(114.1)
461.0
(135.1)
607.6
(178)
885.4
(259.4)
1170
(342.8)
Sensible Capacity, kBTUH (kW)
74.5
(21.8)
104.7
(30.7)
134
(39.3)
158.6
(46.5)
202.3
(59.3)
215.5
(63.1)
260.2
(76.2)
294.9
(86.4)
320.4
(93.9)
389.4
(114.1)
461.0
(135.1)
607.6
(178)
885.4
(259.4)
1170
(342.8)
Flow Rate, GPM (l/s)
13.3
(0.8)
18.7
(1.2)
23.8
(1.5)
28.8
(1.8)
36.4
(2.3)
38.9
(2.5)
46.5
(2.9)
51.8
(3.3)
57.6
(3.6)
69.8
(4.4)
80.8
(5.1)
107.3
(6.8)
155.5
(9.8)
207.6
(13.1)
Pressure Drop, ft (kPA)
6.7
(20.2)
10.6
(31.7)
9.2
(27.7)
5.5
(16.4)
5.7
(17.1)
6.0
(17.9)
10.0
(30.0)
11.4
(34.2)
11.6
(34.8)
19.7
(58.9)
6.1
(18.3)
13.2
(39.6)
5.7
(17.1)
12.4
(37.2)
85°F DB, 64.5°F WB (29.4°C DB, 18.1°C WB) 32.3% RH
Total Capacity, kBTUH (kW)
97.5
(28.60)
132.5
(38.8)
164.2
(48.1)
203.6
(59.7)
248.7
(72.9)
271.5
(79.5)
318.8
(93.4)
356.5
(104.5)
398.9
(116.9)
474.6
(139.1)
565.4
(165.7)
731.1
(214.2)
1088.0
(318.8)
1412.0
(413.7)
Sensible Capacity, kBTUH (kW)
97.5
(28.60)
132.5
(38.8)
164.2
(48.1)
203.6
(59.7)
248.7
(72.9)
271.5
(79.5)
318.8
(93.4)
356.5
(104.5)
398.9
(116.9)
474.6
(139.1)
565.4
(165.7)
731.1
(214.2)
1088.0
(318.8)
1407.0
(412.3)
Flow Rate, GPM (l/s)
17.1
(1.1)
23.4
(1.50)
28.8
(1.80)
36.2
(2.3)
44.1
(2.80)
48.2
(3.0)
56.2
(3.6)
62.0
(3.9)
70.6
(4.5)
83.9
(5.3)
98.2
(6.2)
127.9
(8.1)
189.2
(11.9)
247.9
(15.6)
Pressure Drop, ft (kPA)
10.8
(32.5)
16.1
(48.2)
13.1
(39.2)
8.4
(25.3)
8.1
(24.3)
8.8
(26.5)
14.2
(42.5)
15.9
(47.5)
17.0
(50.7)
27.6
(82.6)
8.7
(26.2)
18.2
(54.4)
8.2
(24.4)
17.2
(51.4)
*
Models CW089, CW146, CW181, CW300 and CW400 available only in downflow.
Содержание CW089
Страница 2: ......
Страница 8: ...Liebert CW System Design Manual vi ...
Страница 10: ...Liebert CW System Design Manual vi Page intentionally left blank ...
Страница 18: ...Nomenclature and Components Liebert CW System Design Manual 8 Page intentionally left blank ...
Страница 62: ...Dimensions Liebert CW System Design Manual 52 Page intentionally left blank ...
Страница 76: ...Piping Liebert CW System Design Manual 66 Page intentionally left blank ...
Страница 90: ...Electrical Field Connections Liebert CW System Design Manual 80 Page intentionally left blank ...
Страница 114: ...Optional Liebert Air Economizer for Liebert CW Liebert CW System Design Manual 104 Page intentionally left blank ...