Guide Specifications—Chilled Water Environmental Control System
Liebert
®
CW
™
System Design Manual
114
3.8
VIRTUAL BACK-DRAFT DAMPER
Liebert iCOM
®
shall allow the use of a virtual back-draft damper, eliminating the need for a mechanical
damper. This shall allow the fans to spin slowly (15% or less) to act as a damper.
3.9
SYSTEM AUTO RESTART
The auto restart feature shall automatically restart the system after a power failure. Time delay shall be
programmable. An optional capacitive buffer may be provided for continuous control operation through a
power failure.
3.10
WIRED SUPPLY SENSOR
Each Liebert iCOM shall have one factory-supplied and connected supply air sensor that may be used as
a controlling sensor or reference. When multiple sensors are applied for control purposes, the user shall be
able to control based on a maximum or average temperature reading.
3.11
SEQUENTIAL LOAD ACTIVATION
On initial startup or restart after power failure, each operational load shall be sequenced with a minimum of
one-second delay to minimize total inrush current.
Содержание CW089
Страница 2: ......
Страница 8: ...Liebert CW System Design Manual vi ...
Страница 10: ...Liebert CW System Design Manual vi Page intentionally left blank ...
Страница 18: ...Nomenclature and Components Liebert CW System Design Manual 8 Page intentionally left blank ...
Страница 62: ...Dimensions Liebert CW System Design Manual 52 Page intentionally left blank ...
Страница 76: ...Piping Liebert CW System Design Manual 66 Page intentionally left blank ...
Страница 90: ...Electrical Field Connections Liebert CW System Design Manual 80 Page intentionally left blank ...
Страница 114: ...Optional Liebert Air Economizer for Liebert CW Liebert CW System Design Manual 104 Page intentionally left blank ...