Anchor and Load Requirements of Seismic Installation
85
Liebert
®
CW
™
System Design Manual
A.3.2 Seismic Connections to Unit
Electrical wiring, conduit, and/or other connections to the equipment is the responsibility of others. Data
and recommendations are supplied here and in the unit installation supplement for seismic installation.
Figure A-1 Field-welding of anchor bracket—Seismic anchorage rigid floor stand, upflow, CW026 – CW114
Upflow Model Number
Dimensional Data in. (mm)
Anchor
Size, in.
A
B
CW026, CW038, CW041
50 (1270)
29 (737)
1/2
CW051, CW060
74 (1880)
29 (737)
1/2
CW076, CW084
99 (2515)
29 (737)
1/2
CW106, CW114
122 (3099)
29 (737)
1/2
Anchor bolt sized per Hilti Kwik Bolt TZ carbon and stainless in concrete, ICC ESR-1917.
Alternates are subject to review by Emerson or engineer of record.
2.6"
67mm
FIELD WELDING OF ANCHOR BRACKET
TYPICAL 4 PLACES
A
B
ANCHOR LOCATION
TYPICAL 6 PLACES
*MIN. EMBEDMENT
*MIN. HOLE DEPTH
(3mm)
TYPICAL BOTH SIDES
1/8"
(3mm)
1.8" (46mm) MINIMUM
1/8"
FLOOR ANCHORING DIMENSIONS
ANSI B18.22.1
TYPE A, SERIES W PLAIN
WASHER REQUIRED AT
EACH ANCHOR LOCAITON
2.3"
59mm
.9"
24mm
3.3"
83mm
2.3"
59mm
* SPECIFIED BY ENGINEER OF RECORD
FRONT
DPN003209
Pg. 2 Rev. 2
Содержание CW089
Страница 2: ......
Страница 8: ...Liebert CW System Design Manual vi ...
Страница 10: ...Liebert CW System Design Manual vi Page intentionally left blank ...
Страница 18: ...Nomenclature and Components Liebert CW System Design Manual 8 Page intentionally left blank ...
Страница 62: ...Dimensions Liebert CW System Design Manual 52 Page intentionally left blank ...
Страница 76: ...Piping Liebert CW System Design Manual 66 Page intentionally left blank ...
Страница 90: ...Electrical Field Connections Liebert CW System Design Manual 80 Page intentionally left blank ...
Страница 114: ...Optional Liebert Air Economizer for Liebert CW Liebert CW System Design Manual 104 Page intentionally left blank ...