EK280
Application Manual
144
9.3
Monthly archive 1 (Monthly meter readings)
In monthly archive 1 meter readings and maximum consumption figures are archived on a monthly basis
based on the monthly limit (= daily limit on the first day of each month) of the previous months.
The content of monthly archive 1 can be shown on the display of the device via the path
"Serv." > "Archives"
> "Monthly Archive 1"
.
i
Monthly archive 1 is a flexible archive.
Archive contents and the memory capacity can be adapted with corresponding settings via
"enSuite" parameterization software when the administrator lock is open.
Our applications team is available if you require further information.
9.3.1
Archive content
Pos. Address
Display
Description
Retrievable
1
01:01F8 GONo
Global Block number
S
2
01:0A20 ABNo
Archive Block number
A + S
3
01:0400 Time
Date and time
A + S
4
02:0300 Vb
Volume at base conditions
A + S
5
02:0302 VbT
Volume at base conditions total
A + S
6
03:0161 VbMP
Maximum VbMP of last month
A + S
7
03:0165 Time
Date and time of Vb.MP
A + S
8
03:0169 Stat
Status of Vb.MP
A + S
9
04:0161 VbDy
Maximum VbDy of last month
A + S
10
04:0165 Time
Date and time of VbDy
A + S
11
04:0169 Stat
Status of VbDy
A + S
12
04:0300 Vm
Volume at measurement conditions
A + S
13
04:0302 VmT
Volume at measurement conditions total
2
A + S
14
10:0161 VmMP
Maximum VmMP of last month
A + S
15
10:0165 Time
Date and time of VmMP
A + S
16
10:0169 Stat
Status of VmMP
A + S
17
11:0161 VmDy
Maximum VmDy of last month
A + S
18
11:0165 Time
Date and time of VmDy
A + S
19
11:0169 Stat
Status of VmDy
A + S
20
02:0110 St.2
Instance-Status 2 (incl. Vn)
A + S
21
04:0110 St.4
Instance -Status 4 (incl. Vb)
A + S
22
03:0A23 ErReg
Error register
A
23
01:0A21 Check
Check sum result (
„CRC OK“ or „Error“)
A + S
The values can be retrieved in accordance with the information in the table via D = display and/or
I = interface.
When using an encoder then the original operating volume "Vo" (01 240) can also be set.
9.3.2
Memory capacity
Based on factory settings, the archive contains 24
data rows, which corresponds to a memory capacity of
approx. 2 years.
i
Monthly archive 1 is a ring-type memory. If the archive is full then the oldest entries are overwritten.
9.3.3
Changing the monthly limit (= daily limit)
See Chapter 9.2.3 Changing the daily limit.
Содержание EK280
Страница 1: ...EK280 Application Manual Issue 2016 1 Software Version 2 31 et seq ...
Страница 2: ......