8.3
Sending SMS messages
If the internal GSM modem is connected (see chapter 7.1) or an external GSM modem respectively an external
device including a GSM modem is connected to the serial interface, the EK280 is able to send SMS messages
(Short Message Service of GSM-Providers) at occurrence of defined events.
i
This function is only available since EK280 software version 2.20.
i
This function creates costs due to data transmission via SMS. Contact your mobile service
provider to get a favorable tariff. It is your responsibility to optimize this cost factor.
i
Due to interference of the radio connection failures may occur in data transmission.
i
This feature only works with a GSM modem.
8.3.1
Preparation
Initial conditions:
-
A GSM modem is applied as described in chapter 7.
-
Transmission of SMS is available with your SIM card.
8.3.2
Parameterization
i
For parameterization of the EK280 you will require a connection cable for the optical interface as
well as the enSuite application at least with version 2.4, which can be downloaded for free at
www.elster.com.
You can find the following menu paths in
enSuite
at
"
Parameterize online
" > "
Parameters
" > "
Interfaces
".
a)
Configure message contents
With enSuite change to the sub-menu "
SMS
" > "
Layouts
"
You can choose between free SMS layouts (no. 1 - 10) and pre-defined SMS layouts (no. 11 -15).
The pre-defined layouts are not changeable and are defined as follows:
Layout
Definition
Volume profile
(11)
The message contains all values of Vm (volume at measurement conditions)
copied from the measure period profile of the last 24 hours beginning at last gas
day start.
Load profile
(12)
The message contains all value changes
∆Vm (volume at measurement
conditions) copied from the measure period profile of the last 24 hours beginning
at last gas day start.
Alarm
(13)
The message contains the information if the EK280 has an active alarm regarding
pressure measurement, temperature measurement or remaining battery lifetime.
Archive entry
(14)
The message contains the latest entry of the measure period profile. The
complete profile line will be transmitted.
Month end value
(15)
The message contains the latest values of Vm and Vb
and their last month‘s
maximum values at end of measure period and start of gas day.