EK280
Application Manual
139
The counter progress compared to the respective previous entry is denoted with a "
". Normally it is a flow
(consumption) in this case within a measurement period. This, however, does not apply when an archive row
is entered due to a particular event (e.g. setting the clock or a counter, appearance of an important status
message). The meter reading flashes with the meter progress to point out this feature to the user (for further
information, refer to the instruction manual “usage as a registration device”).
9.1.2
Memory capacity
Based on factory settings, the archive contains 9504
data rows, which corresponds to a memory capacity of
approx. 13 months with a measurement period of 60 minutes.
i
The measurement period archive is a ring-type memory. If the archive is full then the oldest entries
are overwritten.
9.1.3
Changing the measurement period
All values relating to measurement periods can be created with the measurement period which can be set
here.
In order to set the measurement period on the device to another value, open the administrator or
calibration lock as described in the EK280 operating manual.
i
If at least two entries are still free in the calibration manual then it is possible to change the
measurement periods when the administrator lock is open. Otherwise the value can only be
changed when the calibration lock is open.
Move the cursor in the register
"Serv."
to
"Archives" > "MPer".
Press the ENTER button
One digit of the value flashes.
Move the cursor with the arrow buttons
or
to the digits and change these with the arrow buttons
or
.
i
The measuring period is set to "60 minutes" as standard.
Sensible and typical values include 5, 10, 15, 20, 30 or 60 minutes.
Press the ENTER button to confirm the set value. It is possible to abort the entry by pressing the
ESC button.