Automatic settings
Control System WS1 Color / WS1000 Color
• Version: 14.12.2016 • Technical changes and errors excepted.
Press the button to set the indoor temperature above which the window will be
opened. Until an indoor sensor is selected, the indoor temperature will be disregarded.
Setting the temperature: Adjust the value for the desired room temperature using the
arrow buttons. Pre-setting: 25.0 °C.
The window is opened as soon as the temperature lies above the pre set value. It is
closed again once the temperature sinks more than 2.0°C under the pre-set value (hys-
teresis).
Shutting off ventilation: If ventilation shall be independent of indoor temperature,
press the button labelled
OFF
.
Confirm your setting with the
OK
button.
Press the button to set the air humidity above which the window will be opened. Until
an indoor sensor with humidity measurement is selected, the air humidity will be dis-
regarded.
Setting air humidity: Adjust the value for the desired humidity using the arrow buttons.
Pre-setting: 80%.
The window is opened as soon as the humidity lies above the pre- set value. However,
it is only closed again when the humidity sinks by more than 3.0% under the pre-set
value (hysteresis).
Shutting off ventilation: If ventilation is to be independent of the air humidity, press the
button labelled
OFF
.
Confirm your setting with the
OK
button.
Press the button to set the supply air temperature block (heat protection).
Enable: If the window should be closed when the air supply temperature is higher than
the room temperature, select
Yes
.
The supply air temperature-block becomes active as soon as the incoming air temper-
ature lies above the room temperature. The block is however only deactivated again
when the incoming air temperature sinks below the room temperature by more than
3.0°C (hysteresis).
Disable: If the window should also then be/remain open when the supply air tempera-
ture is higher than the room temperature, select
No
(default setting).
Confirm your setting with the
OK
button.
Indoor Temp.
Air Humidity
Supply-Air Temp.