SINUS-K
PROGRAMMING
MANUAL
69/
226
P32 Out. mon. 4/9
P
P32
R
5÷100 Hz/V
D
10 Hz/V
KOF = *** Hz/V
F
Ratio between output voltage at terminals 17–18 and output frequency, and ratio
between output voltage at terminals 17–18 and frequency reference.
P33 Out. mon. 5/9
P
P33
R
Depending on the inverter size.
D
Depending on the inverter size.
KOI = *** A/V
F
Ratio between inverter output current and output voltage at terminals 17 and 18.
P34 Out. mon. 6/9
P
P34
R
20÷100V/V
D
100 V/V
KOV = *** V/V
F
Ratio between inverter output voltage and output voltage at terminals 17 and 18.
P35 Out. mon. 7/9
P
P35
R
Depending on the inverter size.
D
Depending on the inverter size.
KOP= *** kW/V
F
Ratio between power delivered by the inverter and output voltage at terminals 17
and 18.
P36 Out. mon. 8/9
P
P36
R
90÷10000 rpm/V
D
200 rpm/V
KON*** rpm/V
F
Ratio between motor RPM and output voltage at terminals 17 and 18.
NOTE
Motor RPM is given by Fout (output frequency) multiplied by constant 60 x 2/C58
(parameter Poles, Special function submenu) without considering the motor slip.
P37 Out. mon. 9/9
P
P37
R
2.5÷50 %/V
D
10 %/V
KOR=**.* %/V
F
Ratio between output voltage at terminals 17 & 18 and PID regulator output
(expressed as a percentage) and ratio between output voltage at terminals 17 and
18 and PID regulator feedback value expressed as a percent value.
IFD