PROGRAMMING
SINUS K
MANUAL
74/
226
PARAMETERS OF THE PROHIBIT FREQUENCIES SUBMENU
P55 Prohib.f.2/5
P
P55
R
0÷800 Hz for S05÷S30
0÷120 Hz for S40÷S70
D
0 Hz
Fp1 = ***Hz
F
Determines the intermediate value for the first prohibit frequency range. The
intermediate value is an absolute value, i.e. is not depending on the direction of
rotation. Set it to 0 to disable the prohibit frequency range.
P56 Prohib.f.3/5
P
P56
R
–800÷800 Hz for S05÷S30
–120÷120 Hz for S40÷S70
D
0 Hz
Fp2 = ***Hz
F
Determines the intermediate value for the second prohibit frequency range. The
intermediate value is an absolute value, i.e. is not depending on the direction of
rotation. Set it to 0 to disable the prohibit frequency range.
P57 Prohib.f.4/5
P
P57
R
–800÷800 Hz for S05÷S30
–120÷120 Hz for S40÷S70
D
0 Hz
Fp3 = ***Hz
F
Determines the intermediate value for the third prohibit frequency range. The
intermediate value is an absolute value, i.e. is not depending on the direction of rotation.
Set it to 0 to disable the prohibit frequency range.
P58 Hysteresis 5/5
P
P58
R
0÷24 Hz
D
1 Hz
Fphys = ***Hz
F
Determines the value of semiamplitudes for prohibit frequency ranges.