C59 Brake 12/17
P
C59
disab. = ***** ms
R
0÷65400 ms
D
18000 ms
F
OFF time period of the built–in braking module.
C59=0 braking module always ON; if also C60=0, braking module is always
OFF.
C60 Brake 13/17
P
C60
R
0÷65400 ms
D
2000 ms
enable = ***** ms
F
ON time period of the built–in braking module.
C68=0 braking module always OFF (independently of C59 value).
C61 Speed 14/17
P
C61
R
0÷200%
D
0 %
alarm = *** %
F
Alarm A16 trip (percentage of C02). The alarm threshold trip depends on
formula C02+ C02*C61/100.
If set to 0, this function is disabled.
C62 DCB ramp 15/17
P
C62
R
2÷255 ms
D
100 ms
time = *** ms
F
Flux decreasing ramp before DCB.
C63 Flux 16/17
P
C63
R
30÷4000 ms
D
300 ms for S05÷S30
D
450 ms for S40÷S70
ramp = *** ms
F
Motor flux ramp.
C64 Flux 17/17
P
C63
R
0÷4000 ms
D
0 ms
delay = *** ms
F
Delay time after motor flux ramp before enabling motor startup.
This parameter may be useful if contacts ENABLE (terminal 6) and START
(terminal 7) are to be simultaneously closed.
NOTE
The entire time interval required for the motor fluxing is obtained by summing up the
values of C63 and C64. The motor will start only after this time period is over.