SINUS-K
PROGRAMMING
MANUAL
219/
226
11.6.
SPECIAL PARAMETERS (SPxx) (Write Only)
Description
Addr.
(dec)
Addr.
(hex)
Def Min
Max
K
Unit
of measure
SP01 Terminals simulated from
serial link
768 300
Note 17
SP03 Reference from serial link
770
302
0 IF_C15=0_
–C02_
ELSE_–C42
IF_C15=0_
C02_
ELSE_C42
IF_C15=0_65536/
76444_
ELSE_C04*1000000/
X999*4
IF_C15=0
_rpm_ELSE
_%
X999 Support variable
T000[0]*C06*
1.27845
SP04 PID reference from serial link 771
303
0
–100
100
20
%
SP09
Parameter
saving
776 308
Note 18
SP10
Default
restoration
777 309
Note 19
Note 17 Terminals are simulated by sending a byte to the inverter; the byte bits simulate the active state of an input.
Structure is the same as the one stated in Note 01 (see Note 01). Bit 5 ENABLE is set to AND with the similar bit read
from the terminal board.
Note 18 Any writing with any data item forces the inverter to store to EEPROM all new parameter values.
Note 19 Any writing with any data forces the inverter to restore default programming (factory setting).
Table T000[]: index (SW3) at address 477 (1DDh)
I full scale (A) C63 default
T000[0] T000[1]
0 25
300
1 50
300
2 65
300
3 100
300
4 125
300
5 130
300
6 210
300
7 280
300
8 390
300
9 480
300
10 650
450
11 865
450
12 1300
450
Table T001[]: index (SW5) at address 479 (1DFh)
Class(V)
T001[0]
0 230
1 400
V
T
C