PROGRAMMING
SINUS K
MANUAL
136/
226
NOTE
Select “INV OK OFF” to activate a digital output in the case of emergency (protection
trip; inverter switched off when in emergency mode; inverter turned on with ENABLE
contact (terminal 6) closed and parameter C59 set to [NO]). If “INV OK OFF” is
selected, the digital output may be used to control an indicator light or to send
emergency signals to the PLC. If “Inv run trip” is selected, the digital output activates
only if the inverter enters the emergency mode due to a protection trip. Turn off and
on the equipment in emergency mode to deactivate the digital output. In this
operating mode, the digital output may be used to control a relay activating a
contactor installed on the inverter supply line. The contactor is controlled by an NC
contact in the relay.
NOTE
Use parameter P70 to set a hysteresis for the commutation of a digital output.