PROGRAMMING
SINUS K
MANUAL
178/
226
Error Messages
If a message error is detected, the inverter will send a message to the master:
Slave address
Function (MSB = 1)
Error code
Error correction
The error code meaning is the following:
CODE
NAME
DESCRIPTION
01h
ILLEGAL FUNCTION
The function is not implemented in the slave device
(different from 03h and 10h)
02h
ILLEGAL DATA ADDRESS
The specified address is illegal for the slave device
(1: you attempted to write a Read Only parameter;
2: the address is not included in the lists that follow)
03h
ILLEGAL DATA VALUE
The value is not allowable for the specified location
(it does not range between the values stated in Min / Max columns)
06h
SLAVE DEVICE BUSY
The slave cannot accept writing
(1: you attempted to write a Cxx parameter when the inverter was in RUN mode;
2: a long-lasting operation is occurring, e.g. Restore Default)
9.3.
GENERAL FEATURES and EXAMPLES
Parameters are queried along with the reading performed through the inverter keypad and display. Parameter
alteration is also managed along with the inverter keypad and display. Not that the inverter will always use the latest
value set (sent both via serial link or from the inverter itself).
When writing (10h function: Preset Multiple Register), the inverter will check value ranges only if failures may
occur. If illegal ranges are detected, the inverter will respond with the error message 03h=ILLEGAL DATA VALUE (see
above).
Data are read/written as 16–bit, full data (words) based on scaling factors (K) stated in the tables below.