SINUS-K
PROGRAMMING
MANUAL
105/
226
CAUTION
This parameter is effective for inverter models where fans are controlled by the inverter
control board (“P” or “N” appear in the relevant field – see Section 5.2 Inverter Ratings).
This parameter has no effect for inverter models where fans are controlled directly from
the power circuit (“B ” or “S” appear in the relevant field).
C59 Reduction 7/17
P
C59
R
0.001÷50
D
1
Ratio K = *
F
Proportionality constant between the motor rpm and the value displayed through
parameter M10.
C60 Mains l.m. 8/17
P
C60
R
NO, YES
D
NO
[NO] YES
F
Stores any alarm relating to mains failure (A30 and A31) causing the equipment
power off. When power supply is restored, send a RESET command to reset the
alarms tripped.
C61 ENABLE 9/17
P
C61
R
NO, YES
D
YES
Operation of ENABLE command (terminal 6) at power on or when a RESET
command is sent.
YES: ENABLE activated at power on; if terminals 6 and 7 are active and a
frequency reference is sent, the motor starts at power on or after a few seconds a
RESET command is sent.
[NO] YES
F
NO: ENABLE command deactivated at power on or after RESET; if terminals 6 and
7 are active and a frequency reference is sent at power on or after an alarm RESET,
the motor does not start until terminal 6 is opened and closed again.
DANGER
Setting parameter C61 to YES may start the motor as soon as the inverter is turned on
C62 First 10/17
P
C62
R
Keypad, Status
D
Status
F
Determines which pages are displayed at power on:
Status: Access page to the main menus.
page = ***
Keypad: Page relating to the command sent via keypad.
IFD