PROGRAMMING
SINUS K
MANUAL
226/
226
CAUTION Always reassemble the inverter cover before switching on the inverter.
7 – Turn on the inverter and make sure that SW programming is correct: access the SIZE page containing the inverter
ratings and check that the new application SW is displayed (see step 1 above).
8 – Adjust the parameters relating to the new application SW as explained in this manual.
12.4.
ALARMS RELATING TO SW SELECTION PROCEDURE
If the SW selection procedure is not properly performed, the following alarm conditions may occur:
1)
The inverter does not start. VL LED and IL LED start blinking together (see section 8.3 “DISPLAY AND
INDICATOR LEDS”). This may occur if the SW type in the DSP does not match with the SW installed in the user
interface on FLASH memory (one is programmed with IFD SW and the other is programmed with VTC SW).
Check position of jumpers J15 and J19.
2)
Alarm "A02 Wrong Size" trips: VTC SW was selected for size > S50 . Reset IFD software.
3)
Alarm "A04 Wrong user's parameters" trips: an error was detected in the user parameter memory. Do a
"Restore default" procedure of the user parameters (see Commands Menu).
4)
Alarm “A01 Wrong Software” trips. Please contact ELETTRONICA SANTERNO’s AFTER–SALES SERVICE.