SINUS-K
PROGRAMMING
MANUAL
43/
226
3.11.
PROHIBIT FREQUENCIES/SPEEDS
This function avoids controlling the motor with frequency values corresponding to the machine resonance frequency
(IFD SW) or it prevents the motor from reaching a speed corresponding to the machine resonance frequency (VTC SW).
All parameters relating to this function are included in the Prohibit Frequency/Speed submenu (configuration menu).
Three prohibit frequency/speed ranges may be programmed. To do so, set up intermediate values and a hysteresis
common to all three ranges. Set an intermediate value to zero to disable the relevant prohibit range. The output
frequency/range varies until the new reference value is reached.
Figure0 21: Prohibit frequency/speed ranges.
Use the following parameters to program this function:
– P55: intermediate frequency/speed of the first prohibit range;
– P56: intermediate frequency/speed of the second prohibit range;
– P57: intermediate frequency/speed of the third prohibit range;
– P58: semiamplitude of prohibit ranges (hysteresis).