C26 Op. method 7/12
P
C26
R
Mltf4, Mltr1, DCB, CW/CCW, REV, A/M, Lock, Loc/Rem
D
CW/CCW
Determines functionality of multifunction input 4 (terminal 12):
Mltf4: multifrequency input 4.
Mltr1: variation of acceleration ramp time and deceleration ramp time.
DCB: direct current braking command.
CW/CCW: reversal of the direction of rotation.
REV: reverse rotation command.
A/M: PID regulator deactivation command.
Lock: keypad lock command.
MDI4= ***
F
Loc/Rem: KeyPad mode forced.
C27 Op. method 8/12
P
C27
R
DCB, Mltr2, CW/CCW, V/F2, ExtA, REV, Lock, Fire Mode
D
DCB
Determines functionality of multifunction input 5 (terminal 13):
DCB: direct current braking command.
Mltr2: variation of acceleration ramp time and deceleration ramp time.
CW/CCW: reversal of the direction of rotation.
V/F2: variation of V/f pattern command.
Ext A: auxiliary trip (external alarm).
REV: reverse rotation command.
MDI5= ***
F
Lock: keypad locked.
Fire mode: any protection feature of the inverter is ignored, so that no alarm trips
when the inverter is running.
CAUTION
Due to the activation of the Fire Mode function, the inverter guarantee should be no
longer valid if the conditions for the activation of a protection function occur.
If an asterisk (*) appears next to INVERTER OK on the display, the inverter guarantee is
no longer valid.
C28 PID 9/12
P
C28
R
Ext, Ref F, Add F, Add V
D
Ext
Determines PID regulator operation:
Ext: PID regulator independent of the inverter operation.
Ref F: PID regulator output represents the inverter frequency reference.
Add F: PID regulator output is summed up to the frequency reference.
Action = ***
F
Add V: PID regulator output is summed up to the output voltage value generated by
the selected V/F pattern.
IFD