PROGRAMMING
SINUS K
MANUAL
112/
226
6.3.11.
S
ERIAL
N
ETWORK
S
UBMENU
The Serial Network submenu determines the parameters relating to the serial link.
Access page
Press PROG (Ent) to access the first page of the Serial Network submenu. Press
↑
(Nxt) and
↓
(Prv) to scroll through the
submenus.
First page
Press PROG (Esc) to return to the Serial Network submenu access page. Press
↑
(Nxt) and
↓
(Prv) to scroll through the
parameters.
PARAMETERS OF THE SERIAL NETWORK SUBMENU
C90 Serial 2/7
P
C90
R
1÷247
D
1
Address = *
F
Determines the address assigned to the inverter networked through RS485.
C91 Serial 3/7
P
C91
R
0÷500 ms
D
0 ms
Delay = *** ms
F
Determines the delay between the master query and the inverter response.
C92 Watch Dog 4/7
P
C92
R
NO, YES
D
NO
[NO] YES
F
When active, the inverter locks in remote control mode if no valid message is
received within 5s. Alarm A40 “Serial communication error” is displayed.
C93 RTU Time 5/7
P
C93
R
0÷2000 ms
D
0 ms
out= *** ms
F
When the inverter is ready to receive, the message sent from the master is
considered as complete and processed if no character is received within the time set
through C83.
PROG SAVE
Menu Serial net.
Ent Prv Nxt
PROG SAVE
Serial netw. 1/7
Ent Prv Nxt