PROGRAMMING
SINUS K
MANUAL
198/
226
10.5.
SPECIAL PARAMETERS (SWxx) (Read Only)
Description
Addr.
(dec)
Addr.
(hex)
Min Max
K
SW1 Software
version
475 1DB
Note 13
SW2 Product
ID
476 1DC
Note 14
SW3
AT Full–scale value
477
1DD
0
15
index of T000[]
SW4
Model
478
1DE
0
33
index of T002[]
SW5
Voltage class
479
1DF
0
1
index of T001[]
Note 13 Decimal number corresponding to the inverter firmware version. Example:
Response 2030 = version V2.030
Note 14 ASCII code corresponding to ‘IK’: 494Bh (for 2T and 4T) or to ‘IZ’: 495Ah (for 5T and 6T).
10.6.
SPECIAL PARAMETERS (SPxx) (Write Only)
Description
Addr.
(dec)
Addr.
(hex)
Def Min Max K
Unit
of
measure
SP00 Terminals simulated via serial
link
768 300
Note 15
SP02 Serial
reference
770 302
0 Note 16 Note 16
10 Hz
SP03
Serial PID reference
771
303
0
–100
100
20
%
SP10 Parameter
saving
778 30A
Note 17
SP11 Default
restoration
779 30B
Note 18
Note 15 Terminals are simulated by sending a byte to the inverter; the byte bits simulate the active state of an input.
Structure is the same as the one stated in Note 01 (see Note 01). Bit 5 ENABLE is set to AND with the similar bit read
from the terminal board.
Note 16 Value ranging from –FOMAX1 to FOMAX1 (C07) or from FOMAX2 to FOMAX2 (C13) depending on the
active V/f pattern (selected by MDI5 if C27=3).
Note 17 Any writing with any data item forces the inverter to store to EEPROM all new parameter values.
Note 18 Any writing with any data forces the inverter to restore default programming (factory setting).