KGL Operating Manual – VS 3010 BS
2018-07-02
/
148 178
V. UNLO T ID: XXXXX
Input
Default
Dim.
V. UNLO T C1 XXX s
Only the available capacity stages are displayed.
3..250
20
sec.
V. UNLO T C2 XXX s
3..250
40
sec.
...
V. UNLO T C8 XXX s
3..250
80
sec.
Base module: 1 – max. 4 capacity stages
with first SIOX extension module: 1 – max. 8 capacity stages
Menu 3-2-2 HP control
HP CONT ID: XXXXX
1 Regulation
Continue to menu 3-2-2-1
2 Setpoints
Continue to menu 3-2-2-2
Menu 3-2-2-1 Regulation
HP CONT ID:
XXXXX
Input
Default
Dim.
Type of control
→
Selection list of the HP control type
→
Screen 3-2-2-
1-a
Switch mode
→
Selection list of the HP switching mode (star.delta switching)
→
Screen 3-2-2-
1-b
Fast speed N
X
Fast speed in night operation permitted
↑, ↓, (Y
/N)
Y
-
Del. slow
speed XXs
Delay time until restarting of the fans at slow speed
0..30
5
s
Interval xxs
Interval for calculating the I-component of the fan control
1..60
1
s
Min. Drehzahl
XXX%
Min. fan speed (only visible when the speed controller type of control has been selected - screen 3-2-2-
1-a)
0..50
0
%
Adjust diff. XX
HP controller adjusting speed (only visible when the speed controller type of control has been selected
- screen 3-2-2-1-a)
-15..15
0
-
tc-max. XX°C
max. t for continuous high-pressure regulation (only visible when the speed controller type of control
c
has been selected - screen 3-2-2-1-a)
25..65
40
°C
Fan off w
/comp X
Switch off fan with compressor YES/NO
↑, ↓, (Y
/N)
N
-
Fan off by al.
X
Switch off fans when motor overload cutout is tripped YES/NO
↑, ↓, (Y
/N)
Y
-
Screen 3-2-2-1-a Control type
CONTROL ID: XXXXX
Input
Default
Dim.
Step controller √
Selection list of the HP control type
√
√
-
Speed controller
-
Combi-cont.parall
-
Combi-cont.stages
-
Screen 3-2-2-1-a HP control type - star/delta operation
Switch mode ID: XXXXX
Input
Default
Dim.
Direct √
√
√
-