KGL Operating Manual – VS 3010 BS
2018-07-02
/
173 178
No.
Message text
Message
HP fault Z2 Cx
Oil/HP fault Z2
Compressor x high-pressure fault in Z2 or
Compressor x oil differential pressure switch / HP monitor in Z2 tripped
156
HP fault Z1 Cx
Oil/HP fault Z1
Compressor x high-pressure fault in Z1 or
Compressor x oil differential pressure switch / HP monitor in Z1 tripped
158
Cyl.temp. Z2 Cx
Cylinder head temperature for Z2 compressor x upper threshold
159
Cyl.temp. Z1 Cx
Cylinder head temperature for Z1 compressor x upper threshold
160
HP cutout
High-pressure cutout tripped
162
LP cutout Z2
Z2 low-pressure cutout tripped
163
LP cutout Z1
Z1 low-pressure cutout tripped
165
Low LP Z2
Lower threshold t Z2 circuit undercut
0
166
Low LP Z1
Lower threshold t Z1 circuit undercut
0
167
High HP
Upper threshold t exceeded
c
169
meas. error Z. Z2 Cx
Error in the measuring circuit for measurement of the Z2 compressor x cylinder head temperature
170
meas. error Z. Z1 Cx
Error in the measuring circuit for measurement of the Z1 compressor x cylinder head temperature
171
Meas. error HP
Error in the measuring circuit for measurement of the high-pressure
173
Meas. err. LP Z2
Error in the measuring circuit for measurement of the Z2 low-pressure
174
Meas. err. LP Z1
Error in the measuring circuit for measurement of the Z1 low-pressure
175
Meas. error outdoor
temp.
Error in the measuring circuit for measurement of the outdoor temperature
176
Meas. error Room
temp.
Error in the measuring circuit for measurement of the room temperature
177
Meas. error Humidity
Error in the measuring circuit for measurement of the air humidity
178
Burst disk
Burst disk digital input tripped
179
External alarm
Digital input external alarm is active
180
Service
Service mode has been activated
181
Comp/cond. unload
External unload
183
Load shedding Z2
Z2 compressor disabled due to load shedding
184
Load shedding Z1
Z1 compressor disabled due to load shedding
185
Low refrigerant
Refrigerant level switch tripped
186
Max. speed
Upper threshold value for speed controller exceeded
187
Hand AUS LStufe x
Toggle to Manual OFF
188
Hand EIN LStufe x
Toggle to Manual ON
194
HP cutout D2D Z1
Digital input HP cutout Z1 cases discharge gas defrosting is active (currently not implemented)
195
HP cutout D2D Z2
Digital input HP cutout Z2 cases discharge gas defrosting is active
196
HP cutout D2D Z2R
Digital input HP cutout Z2 cold rooms discharge gas defrosting is active
197
Disable D2D Z1
Digital input disable Z1 cases discharge gas defrosting is active
(currently not implemented)
198
Disable D2D Z2
Digital input disable Z2 cases discharge gas defrosting is active
199
Disable D2D Z2R
Digital input disable Z2 cold rooms discharge gas defrosting is active
200
Fault D2D Z1
Fault in Z1 cases discharge gas defrosting (currently not implemented)
201
Fault D2D Z2
Fault in Z2 cases discharge gas defrosting
202
Fault D2D Z2R
Fault in discharge gas defrosting Z2 cold rooms
203
Sens. type change
A parameter for calibration of the pressure transducers has been changed
205
Z1 compressor stage x has been automatically disabled (5x cylinder temperature too high per day)