KGL Operating Manual – VS 3010 BS
2018-07-02
/
149 178
Switch mode ID: XXXXX
Input
Default
Dim.
Loading and unloading of fan stages sequentially - default operating mode.
Star-delta operation is deactivated
SSFF
Star-delta operation: Fans start one after the other at slow speed (S)
and then switch one after the other to the fast speed (F)
-
SSSF
Star-delta operation: Fans start one after the other at slow speed (S)
and then all switch simultaneously to the fast speed (F)
-
Menu 3 3-2-2 Setpoints HP control
HP CONT ID: XXXXX
Input
Default
Dim.
tcZ1-Max XX°C
max. t -setpoint for setpoint shift Z1
c
0..45
30
°C
tod-min XX°C
Min. outdoor temperature for setpoint shift
0..15
15
°C
tcZ1-Min XX°C
min. t -setpoint for setpoint shift Z1
c
0..35
25
°C
ta-max XX°C
max. outdoor temperature for setpoint shift
16..45
25
°C
HR max. XX°C
t
in the heat recovery mode
c-setpoint
30..50
46
°C
HR dif. XX K
Switching hysteresis in HR mode
1..10
4
K
tc Offset N XX K
t offset in night operation
c
0..15
0
K
Bas. load time F →
Setting of the basic times tb ON
→
Screen 3-2-2-2-a
Var. load time F →
Setting of the variable times tv ON
→
Screen 3-2-2-2-b
Bas.unload time F →
Setting of the basic times tb OFF
→
Screen 3-2-2-2-c
Var.unload time F →
Setting of the variable times tv OFF
→
Screen 3-2-2-2-d
Neutral Zone XX K
Switching hysteresis
1..10
6
K
Control const. XX K
Max. control error for variable control times
1..10
10
K
Screen 3-2-2-2-a Basic time for condenser capacity stages ON
B. LOAD T ID: XXXXX
Input
Default
Dim.
B. LOAD T L1 XXX s
Only the available condenser capacity stages are displayed.
3..250
5
sec.
B. LOAD T L2 XXX s
3..250
10
sec.
...
B. LOAD T L8 XXX s
3..250
60
sec.
Base module: 1 – max. 4 capacity stages
with first SIOX extension module: 1 – max. 8 capacity stages
Screen 3-2-2-2-b Variable time for condenser capacity stages ON
Var. load time F ID: XXXXX
Input
Default
Dim.
V. LOAD T L1 XXX s
Only the available condenser capacity stages are displayed.
3..250
20
sec.
V. LOAD T L2 XXX s
3..250
90
sec.
...
V. LOAD T L9 XXX s
3..250
250
sec.
Base module: 1 – max. 4 capacity stages
with first SIOX extension module: 1 – max. 8 capacity stages
Screen 3-2-2-2-c Basic time for condenser capacity stages OFF