KGL Operating Manual – VS 3010 BS
2018-07-02
/
154 178
Messages ID:
XXXXX
Input
Default
Dim.
Hand LStufe
AUS X
-, 0..
99
Hand LStufe EIN
X
Compressor manual control switch ON
-, 0..
99
0
-
HP cutout D2D
Z1 X
High-pressure cutout for discharge gas defrosting Z1 cases
-, 0..
99
2
-
HP cutout D2D
Z2 X
High-pressure cutout for discharge gas defrosting Z2 cases
-, 0..
99
2
-
HP cutout D2D
Z2R X
High-pressure cutout for discharge gas defrosting Z2 rooms
-, 0..
99
2
-
Disable D2D Z1
X
Disable discharge gas defrosting Z1
-, 0..
99
0
-
Disable D2D Z2
X
Disable discharge gas defrosting Z2
-, 0..
99
0
-
Disable D2D
Z2R X
Disable discharge gas defrosting Z2 cold rooms
-, 0..
99
0
-
Fault D2D Z1 X
Fault in discharge gas defrosting Z1
-, 0..
99
2
-
Fault D2D Z2 X
Fault in discharge gas defrosting Z2
-, 0..
99
2
-
Fault D2D Z2R X
Fault in discharge gas defrosting Z2 cold rooms
-, 0..
99
2
-
änderg.Fühlertyp
X
Sensor match change
-, 0..
99
2
-
Comp auto
disabl. Z1 X
Automatic Z1 compressor disable
-, 0..
99
2
-
Comp auto
disabl. Z2 X
Automatic Z2 compressor disable
-, 0..
99
2
-
No Load Level
Z1 X
No load level received in Z1 (t adjustment)
0
-, 0..
99
2
-
No Load Level
Z2 X
No load level received in Z2 (t adjustment)
0
-, 0..
99
2
-
Speed contr.HP
X
Fault HP speed controller
-, 0..
99
2
-
too many starts
X
For compressor combined control: Starts of the compressors too high
-, 0..
99
2
-
Low SH Z1 X
Minimum superheat Z1 undercut
-, 0..
99
2
-
Low SH Z2 X
Minimum superheat Z2 undercut
-, 0..
99
2
-
Meas. error SH
Z1 X
Measuring circuit fault in suction gas temperature sensor / superheat Z1
-, 0..
99
---
-
Meas. error SH
Z2 X
Measuring circuit fault in suction gas temperature sensor / superheat Z2
-, 0..
99
---
-
Meas. error HP
Z2 X
Measuring circuit fault in pressure transducer for high-pressure Z2
-, 0..
99
2
-
High HP Z2 X
tc/HP Z2 is too high
-, 0..
99
2
-
emerg.cut-out
SH X
Emergency closure of expansion valve(s) due to insufficient superheat
-, 0..
99
0
-
Meas. error R4.1
X
Measuring circuit fault in refrigerant temperature sensor R4.1
-, 0..
99
2
-
Measuring circuit fault in evaporator inlet temperature sensor R5.1
2
-